Section R. 460.20413 - Underground clearances
Universal Citation: MI Admin Code R. 460.20413
Current through Vol. 24-16, September 15, 2024
Rule 413. In addition to the requirements set forth in 49 C.F.R.§192.325, which is adopted by reference in R 460.20606, an operator of pipeline facilities used in the transportation of sour gas shall, if practical, install the pipeline with not less than 48 inches of clearance from all other underground structures not associated with the pipeline. If this clearance cannot be practicably attained, the pipeline shall be protected from damage that might result due to its proximity to the other structure or structures.
Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.