Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Public Service Commission
Michigan Gas Safety Standards
Part 3 - ADDITIONAL MINIMUM SAFETY STANDARDS
Section R. 460.20311 - Test Requirements for pipelines operating below 100 psig
Universal Citation: MI Admin Code R. 460.20311
Current through Vol. 24-16, September 15, 2024
Rule 311. The requirements contained in 49 CFR 192.509(b), which is adopted by reference in R 460.20606, are superseded by both of the following provisions:
(a) An operator shall ensure that all mains are to be pressured tested to at least 90 psig or 1 1/2 times the proposed maximum allowable operating pressure, whichever is greater.
(b) An operator shall ensure that the test pressure is maintained at or above the test pressure requirement for the pipeline being tested for not less than 1 hour. However, the operator shall test a relatively short segment for not less than 30 minutes.
Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.