Part 3 - STORAGE AND HANDLING OF LIQUEFIED HYDROGEN NFPA 50B
Chapter 2 - Design of liquefied hydrogen systems
Section R. 29.7093 - Stationary pumps and compressors

Universal Citation: MI Admin Code R. 29.7093
Current through Vol. 25-4, March 15, 2025

Rule 93. Sections 2-15 to 2-15.5 of the storage and handling of gaseous and Liquefied H2 code are added as follows:

2-15 Stationary pumps and compressors.

2-15.1 Valves shall be installed such that each pump or compressor can be isolated for maintenance. Where pumps or centrifugal compressors are installed for operation in parallel, each discharge line shall be equipped with a check valve to prevent the backflow of liquid from 1 system to the other.

2-15.2 Foundations for cryogenic pumps or compressors shall be designed and constructed to prevent frost heaving.

2-15.3 Operation of all pumps and compressors shall cease when the facility's emergency shutdown device (ESD) system is initiated.

2-15.4 Each pump shall be provided with an adequate vent or relief valve that will prevent over pressurizing of the pump case under normal conditions including the maximum possible rate of cool down.

2-15.5 Vents shall be piped outside of buildings to a point of safe discharge.

Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.