Storage and Handling of Gaseous and Liquefied Hydrogen Systems
Part 3 - STORAGE AND HANDLING OF LIQUEFIED HYDROGEN NFPA 50B
Chapter 2 - Design of liquefied hydrogen systems
Section R. 29.7083 - Testing

Universal Citation: MI Admin Code R. 29.7083
Current through Vol. 25-4, March 15, 2025

Rule 83. Sections 2-5 and 2-5.1 are reproduced from NFPA 50B, and section 2-5.2 of the storage and handling of gaseous and Liquefied H2 code is added as follows:

2-5 Testing.

2-5.1 After installation, all field-erected piping shall be tested and proved hydrogen gas-tight at operating pressure and temperature.

2-5.2 Containers, if out-of-service in excess of 1 year, shall be inspected and tested as outlined in 2-5.1. The pressure relief devices shall be checked to determine if they are operable, properly set, and within test service dates as per section 2-2.15.

Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.