Storage and Handling of Gaseous and Liquefied Hydrogen Systems
Part 2 - STORAGE AND HANDLING OF GASEOUS HYDROGEN NFPA 50A
Chapter 7 - Gaseous hydrogen compression, gas processing, storage, and dispensing systems
Section R. 29.7066 - Emergency shutoff devices

Universal Citation: MI Admin Code R. 29.7066
Current through Vol. 25-4, March 15, 2025

Rule 66. Sections 7-6 to 7-6.1 of the storage and handling of gaseous and Liquefied H2 code are added as follows:

7-6 Emergency shutoff devices.

7-6.1 H2 dispensing systems shall be provided with 1 or more clearly identified emergency shutoff devices or electrical disconnects at the dispensing area. Such devices or disconnects shall be installed in approved locations but not less than 10 feet (3.1 meters) and not more than 100 feet (30.5 meters) away from the dispensing area and which is along the means of egress. Emergency shutoff devices or electrical disconnects shall disconnect power and gas supply to all dispensing devices, to all remote pumps serving the dispensing devices, and to all associated power. When more than 1 emergency shutoff device or electrical disconnect is provided, all devices shall be interconnected. Resetting from an emergency shutoff shall require manual intervention and the manner of resetting shall be approved by the department.

Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.