Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Fire Services
Storage and Handling of Gaseous and Liquefied Hydrogen Systems
Part 2 - STORAGE AND HANDLING OF GASEOUS HYDROGEN NFPA 50A
Chapter 6 - Fire Protection
Section R. 29.7060 - Sprinkler protection
Universal Citation: MI Admin Code R. 29.7060
Current through Vol. 24-16, September 15, 2024
Rule 60. Section 6-5 of the storage and handling of gaseous and Liquefied H2 code is added as follows:
6-5 When sprinkler protection is provided, the area in which H2 is stored or used shall be protected with an automatic sprinkler system designed to be not less than that required by NFPA 13, "standard for the installation of sprinkler systems," adopted by reference in section 8-1.
Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.