Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Fire Services
Storage and Handling of Gaseous and Liquefied Hydrogen Systems
Part 2 - STORAGE AND HANDLING OF GASEOUS HYDROGEN NFPA 50A
Chapter 6 - Fire Protection
Section R. 29.7059 - Fire protection
Universal Citation: MI Admin Code R. 29.7059
Current through Vol. 24-16, September 15, 2024
Rule 59. Section 6-4 of the storage and handling of gaseous and Liquefied H2 code is added as follows:
6-4 A portable fire extinguisher having a rating of not less than 40-B:C, or 2 20-B:C, shall be located within 75 feet (22.9 meters) from the pumps, dispensers, and container fill openings. Fire extinguishers shall be inspected and maintained according to NFPA 10, "standard for portable fire extinguishers," adopted by reference in section 8-1.1.
Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.