Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Fire Services
Storage and Handling of Gaseous and Liquefied Hydrogen Systems
Part 2 - STORAGE AND HANDLING OF GASEOUS HYDROGEN NFPA 50A
Chapter 4 - Design considerations at specific locations
Section R. 29.7044 - Vehicle fueling appliances in nonresidential occupancies
Rule 44. Sections 4-7 to 4-7.7 of the storage and handling of gaseous and Liquefied H2 code are added as follows:
4-7 Vehicle fueling appliances (VFA) in nonresidential occupancies.
4-7.1 VFAs shall not exceed a gas flow of 36 scf/minute.
4-7.2 VFAs shall be listed.
4-7.3 VFAs may be used to fill stationary containers at vehicular fueling locations.
4-7.4 A VFAs installed with storage containers shall comply with the provisions of chapters 2, 3, and 4.
4-7.5 The installation of VFAs at a residence shall comply with the requirements of section 4-9.
4-7.6 Where more than 1 VFA are located in a common area, spacing between the VFAs shall not be less than 3 feet (1 meter), unless permitted in the manufacturer's recommendations.
4-7.7 Unless specifically permitted in the manufacture's recommendations, multiple VFAs shall not be manifolded together on the discharge side.