Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Fire Services
Storage and Handling of Gaseous and Liquefied Hydrogen Systems
Part 2 - STORAGE AND HANDLING OF GASEOUS HYDROGEN NFPA 50A
Chapter 3 - Location of Gaseous Hydrogen Systems
Section R. 29.7034 - Specific requirements

Universal Citation: MI Admin Code R. 29.7034

Current through Vol. 24-16, September 15, 2024

Rule 34. Sections 3-2.1, 3-2.4, 3-2.5, and table 3-2.1 are reproduced from NFPA 50A, and table 3-2.2, sections 3-2.2, 3-2.3 and 3-2.6 to 3-2.9 of the storage and handling of gaseous and Liquefied H2 code are added as follows:

3-2 Specific requirements.

3-2.1 The location of a system, as determined by the maximum total contained volume of H2, shall be in the order of preference as indicated by Roman numerals in table 3-2.1.

Table 3-2.1

Preferred Locations of Gaseous Hydrogen Systems

Nature of Location Size of Hydrogen System
Less than 3500 scf (99 m3) 3500 scf to 15,000 scf (99 m3 to 425 m3) In Excess of 15,000 scf (425 m 3)
Outdoors I I I
In a separate building II II II
In a special room III III Not permitted
Inside buildings not in a special room or exposed to other occupancies IV Not permitted Not permitted

3-2.2 The minimum distance in feet from an H2 system of indicated capacity located either outdoors, in separate buildings, or in special rooms to any specified outdoor exposure shall be in accordance with table 3-2.2. The distances in numbers 1, 3 to 10, and 14 inclusive in table 3-2.2 shall not apply where protective structures having a minimum fire resistance rating of 2 hours are located between the system and the exposure.

(a) An aboveground H2 storage container system shall be erected per table 3-2.2, but not less than 50 feet (22.9 meters), from any of the following:

A school.

A church.

A hospital. A theater.

Assembly occupancy for 50 or more persons.

Exception: The restrictions in section 3-2.2(a) shall not apply to an aboveground H2 system used exclusively for stationary power generation.

Table 3-2.2

Minimum Distance from Outdoor Gaseous Hydrogen Systems to Exposures

Total Gaseous Hydrogen Storage
Type of Outdoor Exposure Less than 3500 scf (99 m3) Feet (meter) 3500 scf to 15,000 scf (99 m3 to 425 m3) Feet (meter) In excess of 15,000 scf (425 m3) Feet (meter)
1. Building or structure (a) Wall(s) adjacent to system constructed of noncombustible or limited&combustible materials
(1) Sprinklered building or structure or unsprinklered building or structure having noncombustible contents 0a (0) 5a (1.5) 5a (1.5)
(2) Unsprinklered building or structure with combustible contents Adjacent wall(s) with fire resistance rating less than 2 hoursb 0c (0) 10 (3.1) 25d (7.6)
Adjacent wall(s) with fire resistance rating of 2 hours or greaterb 0 (0) 5 (1.5) 5 (1.5)
(b) Wall(s) adjacent to system constructed of other than noncombustible or limited&combustible materials 10 (3.1) 25 (7.6) 50d (15.2)
2. Wall openings
(a) Not above any part of a system 10 (3.1) 10 (3.1) 10 (3.1)
(b) Above any part of a system 25 (7.6) 25 (7.6) 25 (7.6)
3. All classes of flammable and combustible liquids above ground 10 (3.1) 25 (7.6) 25 (7.6)
(a) 0-1000 gal (3785L)
(b) In excess of 1000 gal (3785L) 25 (7.6) 50 (15.2) 50 (15.2)
4. All classes of flammable and combustible liquids below ground
0-100 gal (3785L)e 10 (3.1) 10 (3.1) 10 (3.1)

(a) Tank
(b) Vent or fill opening of tank 25 (7.6) 25 (7.6) 25 (7.6)
5. All classes of flammable and combustible liquids below ground in excess of 1000 gal (3785L)e (a) Tank 20 (6.1) 20 (6.1) 20 (6.1)
(b) Vent of fill opening of tank 25 (7.6) 25 (7.6) 25 (7.6)
6. Flammable gas storage (other than H2), either high pressure or low pressure (a) 0&15,000 scf (255 me) capacity 10 (3.1) 25 (7.6) 25 (7.6)
(b) In excess of 15,000 scf (255 me) capacity 25 (7.6) 50 (15.2) 50 (15.2)
7. Oxygen storage (a) 20,000 scf (566 me) or less Refer to NFPA 51, Standard for the Design and Installation of Oxygen&Fuel Gas Systems for Welding, Cutting, and Allied Processes
(b) More than 20,000 scf (566 me) Refer to NFPA 55, Standard for the Storage, Use, and Handling of Compressed Gases and Cryogenic Fluids in Portable and Stationary Containers, Cylinders, and Tanks
8. Fast&burning solids such as ordinary lumber, excelsior, or paper 50 (15.2) 50 (15.2) 5 0 (15.2) 2 5 (7.6) 2 5 (7.6) 5 0 (15.2) 5 0 (15.2) 1 5 (4.6) 5 (1.5) 1 0 (3.1) 1 5 (4.6) 5 0 (15.2)
9. Slow&burning solids such as heavy timber or coal 25 (7.6) 25 (7.6)
10. Open flames and welding 25 (7.6) 25 (7.6)
11. Air compressor intakes or inlets to ventilating or air&conditioning equipment 50 (15.2) 50 (15.2)
12. Places of public assembly less than 50 people 25 (7.6) 50 (15.2)
13 Public sidewalks and parked vehicles 15 (4.6) 15 (4.6)
14 Line of adjoining property that can be built upon 5 (1.5) 5 (1.5)
15. Flammable/Combustible liquid dispenser 10 (3.1) 10 (3.1)
16. Public Way, driveway 15 (4.6) 15 (4.6)
17. Railroad 50 (15.2) 50 (15.2)
a Portions of wall less than 10 ft (3m) (measured horizontally) from any part of a system shall have a fire resistance rating of at least 1/2 hour. bExclusive of windows and doors (see number 2 of Table 3&2.2). cPortions of walls less than 10 ft (3m) (measured horizontally) from any part of a system shall have a fire resistance rating of at least 1 hour. dBut not less than 1/2 the height of adjacent wall of building or structure.

eDistances can be reduced to 15 ft (4.5m) for Class IIIB combustible liquids.

3-2.2.1 Loose or piled combustible material and weeds and long dry grass shall not be within 10 feet (3.1 meters) of any system.

Roof top storage.

Construction of the building/roof that carries the load of the storage tank must carry a minimum 1-hour fire rating.

System must be securely mounted to roof.

System must be located to allow for inspection of the system acceptable to the department based on the best interest of public health, safety, and welfare and the environment.

3-2.3 Unloading connections on delivery equipment shall not be positioned closer to any of the exposures cited in table 3-2.2 than the distances given for the storage system.

(a) H2 transfer between cargo transport vehicle and stationary container systems (single or multiple containers utilizing a common or manifolded transfer line), shall comply with all of the following:

(i) Owners and operators shall ensure that fixed piping is used between the container and master shutoff and check valves. The piping and manifolds shall be secured to the container frame. Flexible hoses are only permitted between the check valve and the cargo vehicle unloading connection.

(ii) Emergency shutoff valves required in this section shall be tested annually for proper operation. The results of the tests shall be documented.

(iii) All installations shall have at least 1 clearly identified and easily accessible manually operated remote emergency shutoff device. Within 1 year after the effective date of these rules, existing installations shall have at least 1 clearly identified and easily accessible manually operated remote emergency shutoff device. The emergency shutoff device shall be located not less than 20 feet (6.1 meters) nor more than 100 feet (30.5 meters) in the path of egress from the emergency shutoff valve and not less than 20 feet (6.1 meters) from the container system.

(iv) During transfer of H2 to and from cargo vehicles, the hand or emergency brake of the vehicle shall be set, and chock blocks shall be used to prevent rolling of the vehicle.

(v) Transfer systems shall be capable of depressurizing to facilitate disconnection. Bleed connections shall lead to a safe point of discharge.

(vi) Cargo vehicle shall be equipped with air-brake interlock in front of the unloading connection to protect against drive-away.

(b) The delivery vehicle shall be located so that all parts of the vehicle are on the premises when delivery is made. Check valves shall be located as close to the container as practical.

(i) Sources of ignition shall not be permitted in the unloading area while transfer is in progress.

3-2.4 H2 systems of less than 3500 scf (99 m3), where located inside buildings and exposed to other occupancies, shall be situated in the building so that the system will be as follows:

(a) In an adequately ventilated area as in 4-2.2.

(b) 20 feet (6.1 meters) from all classes of flammable and combustible liquids, oxidizing gases, and readily combustible materials, such as excelsior and paper.

(c) 25 feet (7.6 meters) from open flames, ordinary electrical equipment, or other sources of ignition .

(d) 50 feet (15.24 meters) from intakes of ventilation or air-conditioning equipment and air compressors.

(e) 50 feet (15.24 meters) from other flammable gas storage.

(f) Protected against damage or injury due to falling objects or working activity in the area. More than one system of 3500 scf (99 cubic meters) or less shall be permitted to be installed in the same room, provided the systems are separated by at least 50 feet (15.24 meters) or where a masonry structure having a minimum fire resistance rating of 2 hours is located between the systems. Each such system shall meet all of the requirements of this section.

Exception: The separation distance between multiple systems of 3500 scf (99 cubic meters) or less shall be permitted to be reduced to 25 feet (7.6 meters) in buildings where the occupancy between storage areas is free of combustible materials and protected with a sprinkler system designed for Ordinary Hazard, Group 1 occupancies or Light Hazard occupancies in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.

3-2.6 An owner and operator shall ensure that a container system, which is underground, mounded, or partially underground, is protected from corrosion by 1 of the following:

(a) The approved container system is cathodically protected by all the following requirements:
(i) The approved container system is coated with a suitable dielectric material approved by the department.

(ii) Factory-installed or field installed cathodic protection systems are designed by a corrosion expert or in accordance with the NACE recommended practice RP0285 entitled "Corrosion Control of Underground Storage Tank Systems by Cathodic Protection," or impressed current systems are designed to allow a determination of current operating status as required in section 5.4-1 of the H2 code.

(iii) Cathodic protection systems are operated and maintained in accordance with the provisions of section 5.4-1 of the H2 code.

(b) The container is made of nonmetallic construction or corrosion-resistant, such as fiberglassor a composite.

(c) Or other means acceptable to the department and based on the best interest of public health, safety, and welfare and the environment.

3-2.7 Out-of-service aboveground containers.

Containers that are no longer in service for a period of 12 months shall be closed. To close the aboveground container, the owner or operator shall empty the container, purge it with an inert gas and safeguard it against tampering. Piping that is removed from service shall be purged with nitrogen and capped or removed.

3-2.7.2 Each container that is to be reused at the original location or a new location shall be purged with an inert gas and be in compliance with all the requirements for the installation of a new container, and shall be recertified by the manufacturer or authorized representative, and tested in accordance with the container's design specifications or be pressure tested with an inert gas or H2 at 1.1 times the MAWP for not less than 10 minutes. Piping that is to be reused shall comply with all the requirements for the installation of new piping and shall be tested in compliance with section 3-2.9 of this code prior to being brought back into service.

3-2.8 Out-of-service underground, mounded, and partially buried containers.

3-2.8.1 Containers that are no longer used to store H2 and are not intended to be brought back into service shall be permanently closed. To permanently close the container, the container shall be emptied and purged with an inert gas to render the container free of H2, and then the container shall be removed from the ground. When a structure above or near the container prevents removal, the container shall be emptied and purged with an inert gas to render the container free of H2, then the container shall be filled with an inert solid material. Piping that is permanently removed from service shall be purged with an inert gas and capped or removed.

3-2.8.2 Containers may be rendered temporarily out-of-service only when it is intended they be brought back into service at a later date. To temporarily close a container, all of the following requirements shall be met:

(a) The container shall be emptied and purged with an inert gas.

(b) Corrosion protection for the container and all underground piping shall be maintained in compliance with section 5-4.1 of this code.

(c) The vent line shall remain functional.

(d) The container shall be secured against tampering.

(e) Piping that is temporarily removed from service shall be purged with an inert gas and capped.

3-2.8.2.1 Each container that is temporarily out of service for greater than 12 months shall be pressure tested with an inert gas at 1.1 times the MAWP for not less than 10 minutes prior to being brought into service. Temporarily out of service piping shall be tested in compliance with section 3-2.9 of this code prior to being brought back into service.

3-2.9 Testing. After installation, prior to being placed into service, all container connections and all fielderected piping, tubing, hose, and hose assemblies shall be tested and proved H2 gas-tight for the rated pressure, volume, and temperature of the gas transported by an approved method as outlined in ASME B31.3, "Process Piping," adopted by reference in section 8-1, or the following:

(a) Perform a pressure test at 1.1 times MAWP, a minimum of 10 minutes.

(b) During pressure test, check for pressure decay. If leakage is detected, use leak detection fluid to find local leaks. Energize the piping with H2 at the MOP, and check for local leaks with a "sonic tester," "sniffer," or method acceptable to the department based on the best interests of public health, safety, welfare and the environment. If the test "fails" the requirements in subsections (a), (b), or (c) of this section, the system must be purged with an inert gas, repaired, and subsections (a), (b), and (c) of this section shall be repeated until the test "passes."

Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.