Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Fire Services
Storage and Handling of Gaseous and Liquefied Hydrogen Systems
Part 2 - STORAGE AND HANDLING OF GASEOUS HYDROGEN NFPA 50A
Chapter 2 - Design of Gaseous Hydrogen Systems
Section R. 29.7029 - Valves
Universal Citation: MI Admin Code R. 29.7029
Current through Vol. 24-16, September 15, 2024
Rule 29. Sections 2-10 to 2-10.2 of the storage and handling of gaseous and Liquefied H2 code are added as follows:
2-10 Valves.
2-10.1 Shutoff valves shall have a rated service pressure not less than the rated service pressure of the entire system and shall be capable of withstanding a hydrostatic test of at least 3 times the rated service pressure without rupture.
2-10.1.1 Leakage shall not occur when tested at least 1.1 times the rated service pressure, using an inert gas compatible with industry practices.
2-10.2 Valves of a design that allows the valve stem to be removed without removal of the complete valve bonnet or without disassembly of the valve body shall not be used.
Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.