Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Fire Services
Storage and Handling of Gaseous and Liquefied Hydrogen Systems
Part 2 - STORAGE AND HANDLING OF GASEOUS HYDROGEN NFPA 50A
Chapter 1 - General information
Section R. 29.7012 - Application
Rule 12. Section 1-3.2 is reproduced from NFPA 50A, and sections 1-3, 1-3.1, 1-3.3, 1-3.4, and 1-3.5 of the storage and handling of gaseous and Liquefied H2 code are added as follows:
1-3 Application.
1-3.1 The application of this standard at places of public assembly shall meet the requirements of section 3-2.2(a) and the approval of the department.
1-3.2 This standard shall not apply to single systems using containers having a total H2 content of less than 400 scf (11 m3). Where individual systems, each having a total H2 content of less than 400 scf (11 m3), are located less than 5 ft (1.5 m) from each other, this standard shall apply.
1-3.3 This standard does not apply to flow-through process containers.
1-3.4 When required by the department, H2 introduced into any system covered by this code shall have a leak detection system acceptable to the department and based on the best interest of public health, safety, and welfare and the environment.