Section R. 29.5664 - Location of loading and unloading facilities

Universal Citation: MI Admin Code R. 29.5664

Current through Vol. 24-04, March 15, 2024

Rule 664. Sections 28.4.2.1 and 28.4.2.2 are added to the FL/CL code as follows:

28.4.2.1 A fire protected tank or a tank in a vault is exempt from compliance with the separation distance requirements for the loading and unloading risers.

28.4.2.2 A tank which has a capacity of 3,000 gallons (11,340 liters) or less which is located 10 feet (3 meters) from any building, and which is provided with spill and audible overfill protection or other means acceptable to the bureau based on the best interests of public health, safety, and welfare and the environment, is exempt from compliance with the separation distance requirements for loading and unloading risers.

Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.