Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Fire Services
New and Existing School, College and University Fire Safety
Part 3 - COLLEGES AND UNIVERSITIES LIFE SAFETY CODE CHAPTERS 1 to 7, 15, 32, AND 33
Section R. 29.1934 - Amendments
Current through Vol. 24-16, September 15, 2024
Rule 34. Sections 39.1.6, 39.3.2.1, 39.3.4.2, and 39.7.2 are amended as follows: 39.1.6. For minimum construction requirements, refer to the Michigan rehabilitation code, R 408.30551 to R 408.30577.
39.3.2.1. Rooms or spaces for the storage, processing, or use of materials specified in section 39.3.2.1(1) to (3) shall be protected pursuant to the following:
(1) The rooms or spaces shall be separated from the remainder of the building by fire barriers having a minimum 1-hour fire resistive rating or protected by automatic extinguishing systems as specified in section 8.7in the following areas:
(2) The rooms or spaces shall be separated from the remainder of the building by fire barriers having a minimum 1-hour fire resistance rating and protected by automatic extinguishing systems as specified in section 8.7in the following areas:
(3) Where automatic extinguishing is used to meet the requirements of section 39.3.2(1) or (2), the protection shall be permitted pursuant to section 9.7.1.2.
39.3.4.2. Initiation of the required fire alarm system shall be by all of the following means where provided:
39.7.2. Fire drills shall be held pursuant to the act.