Section R. 29.2813 - Availability of drawings during inspection
Current through Vol. 24-16, September 15, 2024
Rule 13. A drawing which depicts the completed installation or modification of a required fire alarm system or required fire suppression system as built shall be available to the department of consumer and industry services, office of fire safety, for use during an inspection of a required fire alarm system or required fire suppression system. The drawings and the drawings for all subsequent modifications shall be maintained with the records required by these rules. The drawings shall depict, at a minimum, all of the following:
(a) The location and description of all control devices and equipment of the required fire alarm system or required fire suppression system.
(b) The layout, routing, and sizing of all piping and wiring of the required fire alarm system or required fire suppression system.
(c) The location of all junction boxes and terminations of the required fire alarm system or required fire suppression system.