Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Fire Services
Adult Foster Care Facilities
Part 7 - AMENDMENTS TO THE STANDARD FOR THE INSTALLATION, MAINTENANCE, AND USE OF HOUSEHOLD FIRE WARNING EQUIPMENT (NFPA 74, 1989 EDITION, NATIONAL FI RE PROTECTION ASSOCIATION)
Section R. 400.18702 - Maintenance, tests, and records
Universal Citation: MI Admin Code R. 400.18702
Current through Vol. 24-04, March 15, 2024
Rule 702. Section 6-2 of the standard is amended and section 6-3is added to the standard, to read as follows:
6-2. Tests or inspections, as recommended by the manufacturer, shall be made by the licensee not less than once a month for all smoke detectors.
6-3. Inspections shall be recorded and the records kept on file for 2 years. Records shall be made available upon the request of the authority having jurisdiction.
Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.