Part 7 - AMENDMENTS TO THE STANDARD FOR THE INSTALLATION, MAINTENANCE, AND USE OF HOUSEHOLD FIRE WARNING EQUIPMENT (NFPA 74, 1989 EDITION, NATIONAL FI RE PROTECTION ASSOCIATION)
Section R. 400.18701 - Power supplies

Universal Citation: MI Admin Code R. 400.18701
Current through Vol. 24-04, March 15, 2024

Rule 701. Section 3-1.1.1 of the standard is amended, section 3-2.3 of the standard is deleted, and section 3-5is added to the standard, to read as follows:

3-1.1.1. For electrically powered detectors, an AC primary power source shall be utilized in all new and existing construction.

3-2.3. Deleted.

3-5. A secondary source of power is required and it shall be of sufficient capacity to operate the system for 24 hours and thereafter to sound alarm devices for not less than 4 minutes. A distinctive trouble signal shall be given before the secondary power supply is incapable of operating the equipment for alarm purposes.

Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.