Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Construction Codes
Elevator Safety Board
Michigan Elevator Rules
Chapter 3 - ASME A17.1 MODIFICATIONS
Section R. 408.7058c - Escalator handrail speed-monitoring device

Universal Citation: MI Admin Code R. 408.7058c
Current through Vol. 24-16, September 15, 2024

Rule 58c. Requirement 6.1.6.4 of the ASME A17.1 code is amended to read as follows: A handrail speed monitoring device must be provided that will cause the activation of the alarm required by 6.1.6.3.1(b) without any intentional delay, whenever the speed of either handrail deviates from the step speed by 15% or more. The device must also cause electric power to be removed from the driving-machine motor and brake when the speed deviation of 15% or more is continuous within a 2 s to 6 s range. The device must be of the manual reset type. Automatic resetting of a safety device within these codes is prohibited.

Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.