Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Construction Codes
Elevator Safety Board
Michigan Elevator Rules
Chapter 3 - ASME A17.1 MODIFICATIONS
Section R. 408.7037a - Illumination of cars and lighting fixtures

Universal Citation: MI Admin Code R. 408.7037a

Current through Vol. 24-16, September 15, 2024

Rule 37a. Section 2.14.7.1.4 of ASME A17.1 is amended to read as follows:

2.14.7.1.4 Each elevator must be provided with at least 2 electric light fixtures and a ground fault circuit interrupter duplex receptable on the car top. The 2 light fixtures combined must provide an illumination level of not less than 10 fc at any point on the car top. The light fixtures must be permanent and be of the fixed or portable type and be equipped with guards.

Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.