Section R. 408.7034a - Location of equipment

Universal Citation: MI Admin Code R. 408.7034a

Current through Vol. 24-16, September 15, 2024

Rule 34a. Section 2.7.6.3.2 of the ASME A 17.1 code is amended to read as follows:

2.7.6.3.2 The motor controller must be located in a machinery space within the hoistway, a machine room, or control room. A motor controller may not be located outside the specified rooms or spaces.

Regardless of location, illumination of 19 fc, meaning foot candles, must be provided where controller work is to be performed.

Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.