Rule 547e.
Sections N1103.2.1, N1103.2.2, and N1103.4.2 of the code are amended to read as follows:
N1103.2.1. Insulation (prescriptive). All portions of the air distribution system shall be installed in accordance with Section M1601 and be insulated to an installed R-6 when system components are located within the building but outside the conditioned space, and R-8 when located outside to the building thermal envelope. When located within a building envelope assembly, at least R-8 shall be applied between the duct and that portion of the assembly farthest from conditioned space.
Exception: Portions of the air distribution system within appliances or equipment.
N1103.2.2. Sealing (mandatory). Ducts, air handlers, and filter boxes shall be sealed. Joints and seams shall comply with either the international mechanical code or international residential code, as applicable.
Exceptions:
Duct tightness shall be verified by either of the following:
Exception: The total leakage test is not required for ducts and air handlers located entirely within the building thermal envelope.
N1103.4.2. Hot water pipe insulation (prescriptive). Insulation for hot water pipe with a minimum thermal resistance (R-value) of R-3 shall be applied to the following: