Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Construction Codes
Construction Code Commission General Rules
Construction Code
Part 5 - RESIDENTIAL CODE
Section R. 408.30546 - Smoke alarm locations for existing buildings
Current through Vol. 24-16, September 15, 2024
Rule 546.
Sections R314.2.2, R314.3, R314.3.2, and R314.3.3, R314.4, are amended to the code to read as follows: R314.2.2. Alterations, repairs, and additions. When alterations, repairs, or additions requiring a permit occur, or when 1 or more sleeping rooms are added or created in existing dwellings, the individual dwelling unit shall be equipped with smoke alarms located as required for new dwellings.
Exceptions:
1. Work involving the exterior surfaces of dwellings, such as the replacement of roofing or siding, or the addition or replacement of windows or doors, or the addition of a porch or deck, are exempt from the requirements of this section.
2. Installations, alteration, or repairs of electrical, plumbing, or mechanical systems are exempt from the requirements of this section.
R314.3. Location. Smoke alarms shall be installed in the following locations:
For sleeping units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than 1 full story below the upper level.
Exception: Smoke alarms and devices installed in buildings constructed before November 6, 1974, where an installation was approved by the appropriate enforcing agency under regulations in effect at the time of the installation shall be considered to comply with the provisions of the code.
R314.4. Interconnection. Where more than 1 smoke alarm is required to be installed within an individual dwelling unit in accordance with Section R314.3, the alarm devices shall be interconnected in such a manner that the actuation of 1 alarm will activate all of the alarms in the individual unit. Physical interconnection of smoke alarms shall not be required where listed wireless alarms are installed and all alarms sound upon activation of 1 alarm.
Exception: Interconnection of smoke alarms in existing areas shall not be required.