Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Construction Codes
Construction Code Commission General Rules
Construction Code
Part 5 - RESIDENTIAL CODE
Section R. 408.30537d - Frames of ranges and clothes dryers
Current through Vol. 24-16, September 15, 2024
Rule 537d.
Section E4101.8 of the code is added to read as follows:
E4101.8. Frames of ranges and clothes dryers. Frames of electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and outlet or junction boxes that are part of the circuit for these appliances shall be connected to the equipment grounding conductor in the manner specified in E3908.9. [250.140 amended]
Exception: For existing branch-circuit installations only where an equipment grounding conductor is not present in the outlet or junction box, the frames of electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and outlet or junction boxes that are part of the circuit for these appliances may be connected to the grounded circuit conductor if all of the following conditions are met: [250.140 Exception]