Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Construction Codes
Construction Code Commission General Rules
Construction Code
Part 5 - RESIDENTIAL CODE
Section R. 408.30537c - Devices and luminaires

Universal Citation: MI Admin Code R. 408.30537c

Current through Vol. 24-16, September 15, 2024

Rule 537c.

Sections - E4002.2, and E4002.16, are amended to read as follows:

E4002.2. Grounding type. Receptacles installed on 15- and 20-ampere-rated branch circuits shall be of the grounding type and connected to an equipment grounding conductor.

Exception: Replacement receptacles as permitted by Section E4002.16.

E4002.16. Replacements. Replacement of receptacles shall comply with the following as applicable. [406.4(D) amended]

(1) Grounding-type receptacles. Where a grounding means exists in the receptacle enclosure or an equipment grounding conductor is installed grounding type receptacles shall be used and shall be connected to the equipment grounding conductor. [406.4(D)(1) amended]

(2) Non-grounding-type receptacles. Where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, the installation shall comply with 1 of the following: [406.4(D)(2) amended]
(a) A non-grounding-type receptacle may be replaced with another non-grounding-type receptacle. [406.4(D)(2)(a)]

(b) A non-grounding-type receptacle may be replaced with a ground-fault circuit interrupter-type of receptacle. These receptacles shall be marked "no equipment ground." An equipment grounding conductor shall not be connected from the ground-fault circuit-interrupter-type receptacle to any outlet supplied from the ground-fault circuit-interrupter receptacle. [406.4(D)(2)(b)]

(c) A non-grounding type receptacle may be replaced with a grounding-type receptacle where supplied through a ground-fault circuit interrupter. Grounding-type receptacles supplied through the ground-fault circuit interrupter shall be marked "GFCI protected" and "no equipment ground." An equipment grounding conductor shall not be connected between the grounding-type receptacles. [406.4(D)(2)(c)]

(3) Ground-fault circuit interrupters. Ground-fault circuit-interrupter protected receptacles shall be provided where replacements are made at receptacle outlets that are required to be so protected elsewhere in this code. [406.4(D)(3)]

Exception: Where replacement of the receptacle type is impracticable, such as where the outlet box size will not permit the installation of the GFCI receptacle, the receptacle may be replaced with a new receptacle of the existing type, where GFCI protection is provided and the receptacle is marked "GFCI protected" and "no equipment ground" in accordance with E4002.16 (2)(a), (b),or (c). [406.4(D)(3) Exception]

Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.