Section R. 408.30529 - Lining required
Universal Citation: MI Admin Code R. 408.30529
Current through Vol. 24-16, September 15, 2024
Rule 529.
Section P2709.2 of the code is amended to read as follows:
P2709.2. Lining required. The adjoining walls and floor framing enclosing on-site built-up shower receptors shall be lined with 1 of the following:
1. Sheet lead.
2. Sheet copper.
3. Plastic liner material that complies with
ASTM D 4068 or ASTM D 4551.
4.
Sheet-applied load-bearing, bonded waterproof membranes that comply with ANSI
A118.10.
The lining material shall extend not less than 3 inches (76 mm) beyond or around the rough jambs and not less than 3 inches (76 mm) above finished thresholds. Sheet-applied load bearing, bonded waterproof membranes shall be applied in accordance with the manufacturers instructions.
Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.