Michigan Administrative Code
Department - Licensing and Regulatory Affairs
Bureau of Construction Codes
Construction Code Commission General Rules
Construction Code
Part 4 - BUILDING CODE
Section R. 408.30442 - Automatic sprinkler systems
Universal Citation: MI Admin Code R. 408.30442
Current through Vol. 24-16, September 15, 2024
Rule 442 . Sections 903.2.8, 903.2.8.2, 903.2.5, and 903.2.5.1 are amended and section 903.2.5.4 is added to the code to read as follows:
903.2.8. Group R. An automatic sprinkler system installed in accordance with section 903.3shall be provided throughout all buildings with a Group R fire area.
Exception: Camp buildings in remote areas without municipal water supply that meet all of the following:
1. Not more than 1 story, 2000 square feet
(186 m2) and 25 occupants.
2. Are used not more than 5 months in a
year.
3. Shall be provided with not
less than 2 exits in compliance with section 1019.
4. Shall not be provided with cooking
equipment.
5. Provided with a
manual fire alarm system and smoke alarms throughout in compliance with NFPA 72
as listed in chapter 35. For cabins sleeping 4 or fewer occupants only, smoke
alarms are required.
6. Storage and
equipment rooms shall be protected by a 1-hour fire partition.
7. Compliance with all applicable
requirements of the code.
903.2.8.2. Adult foster care family homes. An
automatic sprinkler system installed in accordance with section 903.3.1.3 shall
be permitted in adult foster care family homes or adult foster care small group
homes for 6 or fewer persons receiving care that are within a single-family
dwelling and licensed in accordance with the adult foster care facility
licensing act, 1979 PA 218, MCL 400.701 to 400.737.
903.2.5. Group H. Automatic sprinkler systems shall be provided in high-hazard occupancies as required in sections 903.2.5.1 to 903.2.5.4.
903.2.5.1. General. An
automatic sprinkler system shall be installed in group H occupancies unless the
requirements of section 903.2.5.4 are met for buildings containing consumer
fireworks.
903.2.5.4. Consumer
fireworks (1.4G). Buildings used for the retail sale of consumer fireworks
shall be provided with an automatic sprinkler system in accordance with the
Michigan fireworks safety act, 2011 PA 256, MCL 28.451 to 28.471.
Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.