Part 10 - MICHIGAN UNIFORM ENERGY CODE
Section R. 408.31063 - Insulation and fenestration criteria

Universal Citation: MI Admin Code R. 408.31063
Current through Vol. 24-16, September 15, 2024

Rule 1063. Insulation and fenestration criteria. Table R402.1.1 of the code is amended to read as follows:

TABLE R 402.1.1 INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa

CLIMATE ZONE

FENESTRATION U-FACTOR

SKYLIGHTb

U-FACTOR

CEILING R-Value

WOOD FRAME WALL R-VALUE

MASS WALL R-VALUEg

FLOOR

R-VALUE

BASEMENTc

WALL R-VALUE

SLAB d

R-VALUE

AND DEPTH

CRAWL

SPACEc

WALL R-VALUE

5A

0.32

0.55

38

20 or 13 + 5f

13/17

30e

10/13

10, 2ft

15/19

6A

0.32

0.55

49

20 or 13 + 5f

15/20

30e

15/19

10, 4ft

15/19

7

0.32

0.55

49

20 or 13

+ 5f

19/21

38e

15/19

10, 4ft

15/19

a. R-values are minimums. U-factors are maximums. When insulation is installed in a cavity that is less than the label or design thickness of the insulation, the installed R-value of the insulation shall not be less than the R-values specified in the table.

b. The fenestration U-factor column excludes skylights.

c. "15/19" means R-15 continuous insulation on the interior or exterior of the home or R-19 cavity insulation at the interior of the basement wall. "15/19" may be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the home. "10/13" means R-10 continuous insulation on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall.

d. R-5 shall be added to the required slab edge R-values for heated slabs.

e. Or insulation sufficient to fill the framing cavity, R-19 minimum.

f. First value is cavity insulation, second is continuous insulation or insulated siding, so "13 + 5" means R-13 cavity insulation plus R-5 continuous insulation or insulated siding. If structural sheathing covers 40 % or less of the exterior, continuous insulation R-value may be reduced by no more than R-3 in the locations where structural sheathing is used to maintain a consistent total sheathing thickness.

g. The second R-value applies when more than half the insulation is on the interior of the mass wall.

Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.