Rule 7225.

(1) A Class I flammable solvent stored inside a building shall be in an approved safety can with an automatic closing cap and flame arrestor or original unopened container having a capacity of not more than 5 gallons. Quantities in excess of 5 gallons shall be stored as prescribed by flammable liquid regulations of the fire marshal promulgated under 1941 PA 207.

(2) When pouring a flammable solvent from 1 container to another, continuous contact between the containers shall be maintained or a bonding or grounding strap shall connect the containers.

(3) A Class I flammable solvent shall not be used for cleaning tools, parts, floors, or booths.

(4) When a flammable liquid is removed from a vehicle tank, an approved pumping device equipped with a ground strap shall be used.

Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.