Part 8 - HANDLING AND STORAGE OF MATERIALS
Section R. 408.40822 - Clearances
Universal Citation: MI Admin Code R. 408.40822
Current through Vol. 24-16, September 15, 2024
Rule 822.
(1) Material stored near an electrical distribution or transmission line shall maintain the following clearances:
(a) Line
rated 50 kV or less--10 feet plus length of material stored.
(b) Line rated 50 kV or more--10 feet plus
0.4 inch for each 1 kV over 50 kV plus length of material stored or 10 feet
plus 4 inches for each 10 kV over 50 kV plus length of material
stored.
(2) An employee shall be designated to observe the clearance and give timely warning if it is difficult for the operator to maintain the prescribed clearance by visual means.
Disclaimer: These regulations may not be the most recent version. Michigan may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.