Add section R314.9 Common Areas as follows:

R314.9 Common Areas. In all buildings that are not protected with sprinklers, each unit shall have additional interconnected smoke detectors on the stairway side of all doors leading to common interior stairways. If there is a common basement, a separate interconnected system of smoke detectors, including smoke detectors on the stairway side of all doors leading to interior stairways, shall be provided to the basement level only.

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.