Code of Massachusetts Regulations
780 CMR - STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
Chapter CHAPTER 51 - MASSACHUSETTS RESIDENTIAL CODE
Appendix AF - RADON CONTROL METHODS - ADOPT AS REVISED
Section AF103.4

Current through Register 1543, March 14, 2025

Revise and replace section AF103.4.4 Sumps as follows:

AF103.4.4 Sumps. Sumps open to soil or serving as the termination point for sub-slab drain tile loops shall be covered with a gasketed or sealed lid. Sumps used as the suction point in a sub slab depressurization system shall have a lid designed to accommodate the vent pipe. Sumps used as a floor drain shall have a lid equipped with a trapped inlet. Drainage systems that lead outside the foundation walls shall be isolated or trapped so as not to short-circuit the depressurization system.

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.