Section 913 - FIRE PUMPS
Subsection 913.4 - Valve supervision
Universal Citation: 780 CMR MA Code of Regs 913.4
Current through Register 1531, September 27, 2024
Where provided, the fire pump suction, discharge and bypass valves, and isolation valves on the backflow prevention device or assembly shall be supervised open by one of the following methods: [F]
1. Central-station, proprietary or remote-station signaling service.
2. Local signaling service that will cause the sounding of an audible signal at a constantly attended location.
3. Locking valves open.
4. Sealing of valves and approved weekly recorded inspection where valves are located within fenced enclosures under the control of the owner.
913.4.1
Test outlet valve supervision.
Fire pump test outlet valves shall be supervised in the closed position.
[F]
Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.