Code of Massachusetts Regulations
780 CMR - STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
Chapter 9 - Fire Protection Systems
Section 909 - SMOKE CONTROL SYSTEMS
Subsection 909.5 - Smoke barrier construction
Current through Register 1531, September 27, 2024
Smoke barriers shall comply with Section 710, and shall be constructed and sealed to limit leakage areas exclusive of protected openings. The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios: [F]
1. Walls: | A/A w = 0.00100 |
2. Exit enclosures: | A/A w = 0.00035 |
3. All other shafts: | A/A w = 0.00150 |
4. Floors and roofs: | A/A F = 0.00050 |
where:
A = Total leakage area, square feet (m2).
AF= Unit floor or roof area of barrier, square feet (m2).
Aw= Unit wall area of barrier, square feet (m2).
The leakage area ratios shown do not include openings due to doors, operable windows or similar gaps. These shall be included in calculating the total leakage area.
909.5.1 Leakage area. The total leakage area of the barrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio, plus the area of other openings such as gaps and operable windows. Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems. Passive smoke control systems tested using other approved means such as door fan testing shall be as approved by the fire code official. [F]
909.5.2 Opening protection. Openings in smoke barriers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system. Door openings shall be protected by fire door assemblies complying with Section 715.4.3. [F]
Exceptions: