Code of Massachusetts Regulations
780 CMR - STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
Chapter 9 - Fire Protection Systems
Section 907 - FIRE ALARM AND DETECTION SYSTEMS
Subsection 907.7 - Acceptance tests and completion
Current through Register 1531, September 27, 2024
Upon completion of the installation, the fire alarm system and all fire alarm components shall be tested in accordance with NFPA 72. [F]
907.7.1 Single- and multiple-station alarm devices. When the installation of the alarm devices is complete, each device and interconnecting wiring for multiple-station alarm devices shall be tested in accordance with the smoke alarm provisions of NFPA 72. [F]
907.7.2 Record of completion. A record of completion in accordance with NFPA 72 verifying that the system has been installed and tested in accordance with the approved plans and specifications shall be provided. [F]
907.7.3 Instructions. Operating, testing and maintenance instructions and record drawings ("as-builts") and equipment specifications shall be provided at an approved location. [F]