Section 906 - PORTABLE FIRE EXTINGUISHERS
Subsection 906.3 - Size and distribution
Current through Register 1531, September 27, 2024
The size and distribution of portable fire extinguishers shall be in accordance with Sections 906.3.1 through 906.3.4. [F]
TABLE 906.3(1) FIRE EXTINGUISHERS FOR CLASS A FIRE HAZARDS [F]
LIGHT
(Low) HAZARD OCCUPANCY |
ORDINARY (Moderate)
HAZARD OCCUPANCY |
EXTRA
(High) HAZARD OCCUPANCY |
|
Minimum Rated Single Extinguisher | 2-A c | 2-A | 4-A a |
Maximum Floor Area Per Unit of A | 3,000 square feet | 1,500 square feet | 1,000 square feet |
Maximum Floor Area for Extinguisherb | 11,250 square feet |
11,250 square feet | 11,250 square feet |
Maximum Travel Distance to Extinguisher | 75 feet | 75 feet | 75 feet |
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929m2, 1
gallon = 3.785 L. a. Two 21/2-gallon water-type extinguishers shall be deemed the equivalent of one 4-A rated extinguisher. b. Annex E.3.3 of NFPA 10 provides more details concerning application of the maximum floor area criteria. c. Two water-type extinguishers each with a 1-A rating shall be deemed the equivalent of one 2-A rated extinguisher for Light (Low) Hazard Occupancies. |
TABLE 906.3(2) FLAMMABLE OR COMBUSTIBLE LIQUIDS WITH DEPTHS LESS THAN OR EQUAL TO 0.25 INCH [F]
TYPE OF HAZARD | BASIC MINIMUM EXTINGUISHER RATING |
MAXIMUM TRAVEL DISTANCE TO EXTINGUISHERS (feet) |
Light (Low) | 5-B 10-B |
30 50 |
Ordinary (Moderate) | 10-B 20-B |
30 50 |
Extra (High) | 40-B 80-B |
30 50 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
Note: For requirements on water-soluble flammable liquids and alternative sizing criteria, see Section 5.5 of NFPA 10. |
906.3.1 Class A fire hazards. The minimum sizes and distribution of portable fire extinguishers for occupancies that involve primarily Class A fire hazards shall comply with Table 906.3(1). [F]
906.3.2 Class B fire hazards. Portable fire extinguishers for occupancies involving flammable or combustible liquids with depths less than or equal to 0.25-inch (6.35 mm) shall be selected and placed in accordance with Table 906.3(2). [F]
Portable fire extinguishers for occupancies involving flammable or combustible liquids with a depth of greater than 0.25-inch (6.35 mm) shall be selected and placed in accordance with NFPA 10.
906.3.3 Class C fire hazards. Portable fire extinguishers for Class C fire hazards shall be selected and placed on the basis of the anticipated Class A or B hazard. [F]
906.3.4 Class D fire hazards. Portable fire extinguishers for occupancies involving combustible metals shall be selected and placed in accordance with NFPA 10. [F]