Code of Massachusetts Regulations
780 CMR - STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
Chapter 9 - Fire Protection Systems
Section 906 - PORTABLE FIRE EXTINGUISHERS
Subsection 906.2 - General requirements
Current through Register 1531, September 27, 2024
Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. [F]
Exceptions:
1. The travel distance to reach an extinguisher shall not apply to the spectator seating portions of Group A-5 occupancies.
2. Thirty-day inspections shall not be required and maintenance shall be allowed to be once every three years for dry-chemical or halogenated agent portable fire extinguishers that are supervised by a listed and approved electronic monitoring device, provided that all of the following conditions are met:
3. In Group I-3 occupancies, portable fire extinguishers are permitted to be located at staff locations.