Chapter 9 - Fire Protection Systems
Section 905 - STANDPIPE SYSTEMS
Subsection 905.6 - Location of Class III standpipe hose connections

Universal Citation: 780 CMR MA Code of Regs 905.6

Current through Register 1531, September 27, 2024

Class III standpipe systems shall have hose connections located as required for Class I standpipes in Section 905.4 and shall have Class II hose connections as required in Section 905.5. [F]

905.6.1 Protection. Risers and laterals of Class III standpipe systems shall be protected as required for Class I systems in accordance with Section 905.4.1. [F]

905.6.2 Interconnection. In buildings where more than one Class III standpipe is provided, the standpipes shall be interconnected in accordance with NFPA 14. [F]

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.