Chapter 9 - Fire Protection Systems
Section 901 - GENERAL
Subsection 901.6 - Supervisory service
Current through Register 1531, September 27, 2024
Where required, fire protection systems shall be monitored by an approved supervising station in accordance with NFPA 72.
901.6.1 Automatic sprinkler systems. Automatic sprinkler systems shall be monitored by an approved supervising station.
Exceptions:
901.6.2 Fire alarm systems. Fire alarm systems required by the provisions of Section 907.2 of this code and Sections 907.2 and 907.3 of the International Fire Code shall be monitored by an approved supervising station in accordance with Section 907.6.5.
Exceptions:
901.6.3 Group H. Manual fire alarm, automatic fire-extinguishing and emergency alarm systems in Group H occupancies shall be monitored by an approved supervising station.
Exception: When approved by the building official, on-site monitoring at a constantly attended location shall be permitted provided that notifications to the fire department will be equal to those provided by an approved supervising station.