Code of Massachusetts Regulations
780 CMR - STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
Chapter 7 - Fire and Smoke Protection Features
Section 721 - CALCULATED FIRE RESISTANCE
Subsection 721.6 - Wood assemblies
Current through Register 1531, September 27, 2024
The provisions of this section contain procedures by which the fire-resistance ratings of wood assemblies are established by calculations.
721.6.1 General. This section contains procedures for calculating the fire-resistance ratings of walls, floor/ceiling and roof/ceiling assemblies based in part on the standard method of testing referenced in Section 703.2.
721.6.2 Walls, floors and roofs. These procedures apply to both load-bearing and nonload-bearing assemblies.
TABLE 721.6.2(1) TIME ASSIGNED TO WALLBOARD MEMBRANESa, b, c, d
DESCRIPTION OF FINISH | TIMEe(minutes) |
3/8-inch wood structural panel bonded with exterior glue | 5 |
15/32-inch wood structural panel bonded with exterior glue | 10 |
19/32-inch wood structural panel bonded with exterior glue | 15 |
3/8-inch gypsum wallboard | 10 |
1/2-inch gypsum wallboard | 15 |
5/8-inch gypsum wallboard | 30 |
1/2-inch Type X gypsum wallboard | 25 |
5/8-inch Type X gypsum wallboard | 40 |
Double 3/8-inch gypsum wallboard | 25 |
1/2-inch + 3/8-inch gypsum wallboard | 35 |
Double 1/2-inch gypsum wallboard | 40 |
For SI: 1 inch = 25.4 mm. |
a. These values apply only when membranes are installed on framing members which are spaced 16 inches o.c. |
b. Gypsum wallboard installed over framing or furring shall be installed so that all edges are supported, except 5/8-inch Type X gypsum wallboard shall be permitted to be installed horizontally with the horizontal joints staggered 24 inches each side and unsupported but finished. |
c. On wood frame floor/ceiling or roof/ceiling assemblies, gypsum board shall be installed with the long dimension perpendicular to framing members and shall have all joints finished. |
d. The membrane on the unexposed side shall not be included in determining the fire resistance of the assembly. When dissimilar membranes are used on a wall assembly, the calculation shall be made from the least fire-resistant (weaker) side. |
e. The time assigned is not a finished rating. |
TABLE 721.6.2(2) TIME ASSIGNED FOR CONTRIBUTION OF WOOD FRAME a, b, c
DESCRIPTION | TIME ASSIGNED TO FRAME (minutes) |
Wood studs 16 inches o.c. | 20 |
Wood floor and roof joists 16 inches o.c. | 10 |
For SI: 1 inch = 25.4 mm. |
a. This table does not apply to studs or joists spaced more than 16 inches o.c. |
b. All studs shall be nominal 2 * 4 and all joists shall have a nominal thickness of at least 2 inches. |
c. Allowable spans for joists shall be determined in accordance with Sections 2308.8, 2308.10.2 and 2308.10.3. |
TABLE 721.6.2(3) MEMBRANEa ON EXTERIOR FACE OF WOOD STUD WALLS
SHEATHING | PAPER | EXTERIOR FINISH |
5/8-inch T & G lumber | Lumber siding | |
5/16-inch exterior glue wood structural panel | Sheathing paper | Wood shingles and shakes |
1/2-inch gypsum wallboard | 1/4-inch wood structural panels-exterior type | |
5/8-inch gypsum wallboard | 1/4-inch hardboard | |
1/2-inch fiberboard | Metal siding | |
Stucco on metal lath | ||
Masonry veneer | ||
Vinyl siding | ||
None | - | 3/8-inch exterior-grade wood structural panels |
For SI: 1 inch = 25.4 mm. |
a. Any combination of sheathing, paper and exterior finish is permitted. |
TABLE 721.6.2(4) FLOORING OR ROOFING OVER WOOD FRAMINGa
ASSEMBLY | STRUCTURAL MEMBERS | SUBFLOOR OR ROOF DECK | FINISHED FLOORING OR ROOFING |
Floor | Wood | 15/32-inch wood structural panels or 11/16 inch T & G softwood | Hardwood or softwood flooring on building paper resilient
flooring, parquet floor felted-synthetic fiber floor coverings, carpeting, or
ceramic tile on
3/8-inch-thick panel-type
underlay Ceramic tile on 11/4-inch mortar bed |
Roof | Wood | 15/32-inch wood structural panels or 11/16 inch T & G softwood | Finished roofing material with or without insulation |
For SI: 1 inch = 25.4 mm. |
a. This table applies only to wood joist construction. It is not applicable to wood truss construction. |
TABLE 721.6.2(5) TIME ASSIGNED FOR ADDITIONAL PROTECTION
DESCRIPTION OF ADDITIONAL PROTECTION | FIRE RESISTANCE (minutes) |
Add to the fire-resistance rating of wood stud walls if the spaces between the studs are completely filled with glass fiber mineral wool batts weighing not less than 2 pounds per cubic foot (0.6 pound per square foot of wall surface) or rockwool or slag material wool batts weighing not less than 3.3 pounds per cubic foot (1 pound per square foot of wall surface), or cellulose insulation having a nominal density not less than 2.6 pounds per cubic foot. | 15 |
For SI: 1 pound per cubic foot = 16.02 kg/m3, 1 pound per square foot = 4.882 kg/m2. |
721.6.3 Design of fire-resistant exposed wood members. The fire-resistance rating, in minutes, of timber beams and columns with a minimum nominal dimension of 6 inches (152 mm) is equal to:
Beams: | 2.54Zb [4 -2(b/d)] for beams which may be exposed to fire on four sides. | (Equation 7-18) |
2.54Zb [4 -(b/d)] for beams which may be exposed to fire on three sides. | (Equation 7-19) | |
Columns: | 2.54Zd [3 -(d/b)] for columns which may be exposed to fire on four sides | (Equation 7-20) |
2.54Zd [3 -(d/2b)] for columns which may be exposed to fire on three sides. | (Equation 7-21) |
where:
b = The breadth (width) of a beam or larger side of a column before exposure to fire (inches).
d = The depth of a beam or smaller side of a column before exposure to fire (inches).
Z = Load factor, based on Figure 721.6.3(1).
FIGURE 721.6.3(1) LOAD FIGURE
Ke = The effective length factor as noted in Figure 721.6.3(2). |
l = The unsupported length of columns (inches). |
FIGURE 721.6.3(2) EFFECTIVE LENGTH FACTORS