Code of Massachusetts Regulations
780 CMR - STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
Chapter 7 - Fire and Smoke Protection Features
Section 721 - CALCULATED FIRE RESISTANCE
Subsection 721.2 - Concrete assemblies
Current through Register 1531, September 27, 2024
The provisions of this section contain procedures by which the fire-resistance ratings of concrete assemblies are established by calculations.
721.2.1 Concrete walls. Cast-in-place and precast concrete walls shall comply with Section 721.2.1.1. Multiwythe concrete walls shall comply with Section 721.2.1.2. Joints between precast panels shall comply with Section 721.2.1.3. Concrete walls with gypsum wallboard or plaster finish shall comply with Section 721.2.1.4.
TABLE 721.2.1.1 MINIMUM EQUIVALENT THICKNESS OF CAST-IN-PLACE OR PRECAST CONCRETE WALLS, LOAD-BEARING OR NONLOAD-BEARING
CONCRETE TYPE | MINIMUM SLAB THICKNESS (inches) FOR FIRE-RESISTANCE RATING OF | ||||
1-hour | 11/2-hour | 2-hour | 3-hour | 4-hour | |
Siliceous | 3.5 | 4.3 | 5.0 | 6.2 | 7.0 |
Carbonate | 3.2 | 4.0 | 4.6 | 5.7 | 6.6 |
Sand-lightweight | 2.7 | 3.3 | 3.8 | 4.6 | 5.4 |
Lightweight | 2.5 | 3.1 | 3.6 | 4.4 | 5.1 |
For SI: 1 inch = 25.4 mm. |
For s >= 4t, the thickness to be used shall be t
For s <= 2t, the thickness to be used shall be te
For 4t> s > 2t, the thickness to be used shall be
Click to view image | (Equation 7-3) |
where:
s = Spacing of ribs or undulations.
t = Minimum thickness.
te = Equivalent thickness of the panel calculated as the net cross-sectional area of the panel divided by the width, in which the maximum thickness used in the calculation shall not exceed 2t.
TABLE 721.2.1.2(1) VALUES OF Rn0.59 FOR USE IN EQUATION 7-4
TYPE OF MATERIAL | THICKNESS OF MATERIAL (inches) | |||||||||||
11/2 | 2 | 21/2 | 3 | 31/2 | 4 | 41/2 | 5 | 51/2 | 6 | 61/2 | 7 | |
Siliceous aggregate concrete | 5.3 | 6.5 | 8.1 | 9.5 | 11.3 | 13.0 | 14.9 | 16.9 | 18.8 | 20.7 | 22.8 | 25.1 |
Carbonate aggregate concrete | 5.5 | 7.1 | 8.9 | 10.4 | 12.0 | 14.0 | 16.2 | 18.1 | 20.3 | 21.9 | 24.7 | 27.2c |
Sand-lightweight concrete | 6.5 | 8.2 | 10.5 | 12.8 | 15.5 | 18.1 | 20.7 | 23.3 | 26.0c | Note c | Note c | Note c |
Lightweight concrete | 6.6 | 8.8 | 11.2 | 13.7 | 16.5 | 19.1 | 21.9 | 24.7 | 27.8c | Note c | Note c | Note c |
Insulating concretea | 9.3 | 13.3 | 16.6 | 18.3 | 23.1 | 26.5c | Note c | Note c | Note c | Note c | Note c | Note c |
Airspaceb | - | - | - | - | - | - | - | - | - | - | - | - |
For SI: 1 inch = 25.4 mm, 1 pound per cubic foot = 16.02 kg/m3. |
a. Dry unit weight of 35 pcf or less and consisting of cellular, perlite or vermiculite concrete. |
b. The Rn 0.59 value for one 1/2" to 3 1/2" airspace is 3.3. The Rn 0.59 value for two 1/2" to 3 1/2" airspaces is 6.7. |
c. The fire-resistance rating for this thickness exceeds 4 hours. |
TABLE 721.2.1.2(2) FIRE-RESISTANCE RATINGS BASED ON RO.59
Ra, MINUTES | R 0.59 |
60 | 11.20 |
120 | 16.85 |
180 | 21.41 |
240 | 25.37 |
a. Based on Equation 7-4. |
For SI: 1 inch = 25.4 mm. |
FIGURE 721.2.1.2 FIRE-RESISTANCE RATINGS OF TWO-WYTHE CONCRETE WALLS
R = (R 10.59 + R 20.59 + ... + Rn 0.59)1.7 | (Equation 7-4) |
where:
R = The fire endurance of the assembly, minutes.
R 1, R 2, and Rn = The fire endurances of the individual wythes, minutes. Values of Rn0.59 for use in Equation 7-4 are given in Table 721.2.1.2(1). Calculated fire-resistance ratings are shown in Table 721.2.1.2(2).
For SI: 1 inch = 25.4 mm. |
FIGURE 721.2.1.3.1 CERAMIC FIBER JOINT PROTECTION
TABLE 721.2.1.4(1) MULTIPLYING FACTOR FOR FINISHES ON NONFIRE-EXPOSED SIDE OF WALL
TYPE OF FINISH APPLIED TO CONCRETE OR CONCRETE MASONRY WALL | TYPE OF AGGREGATE USED IN CONCRETE OR CONCRETE MASONRY | |||
Concrete: siliceous or carbonate Concrete Masonry: siliceous or carbonate; solid clay brick | Concrete: sand-lightweight Concrete Masonry: clay tile; hollow clay brick; concrete masonry units of expanded shale and <20% sand | Concrete: lightweight Concrete Masonry: concrete masonry units of expanded shale, expanded clay, expanded slag, or pumice < 20% sand | Concrete Masonry: concrete masonry units of expanded slag, expanded clay, or pumice | |
Portland cement-sand plaster | 1.00 | 0.75a | 0.75a | 0.50a |
Gypsum-sand plaster | 1.25 | 1.00 | 1.00 | 1.00 |
Gypsum-vermiculite or perlite plaster | 1.75 | 1.50 | 1.25 | 1.25 |
Gypsum wallboard | 3.00 | 2.25 | 2.25 | 2.25 |
For SI: 1 inch = 25.4 mm. |
a. For portland cement-sand plaster 5/8 inch or less in thickness and applied directly to the concrete or concrete masonry on the nonfire-exposed side of the wall, the multiplying factor shall be 1.00. |
TABLE 721.2.1.4(2) TIME ASSIGNED TO FINISH MATERIALS ON FIRE-EXPOSED SIDE OF WALL
FINISH DESCRIPTION | TIME (minute) |
Gypsum wallboard | |
3/8 inch | 10 |
1/2 inch | 15 |
5/8 inch | 20 |
2 layers of 3/8 inch | 25 |
1 layer 3/8 inch, 1 layer 1/2 inch | 35 |
2 layers 1/2 inch | 40 |
Type X gypsum wallboard | |
1/2 inch | 25 |
5/8 inch | 40 |
Portland cement-sand plaster applied directly to concrete masonry | See Note a |
Portland cement-sand plaster on metal lath | |
3/4 inch | 20 |
7/8 inch | 25 |
1 inch | 30 |
Gypsum sand plaster on 3/8-inch gypsum lath | |
1/2 inch | 35 |
5/8 inch | 40 |
3/4 inch | 50 |
Gypsum sand plaster on metal lath | |
3/4 inch | 50 |
7/8 inch | 60 |
1 inch | 80 |
For SI: 1 inch = 25.4 mm. |
a. The actual thickness of portland cement-sand plaster, provided it is 5/8 inch or less in thickness, shall be permitted to be included in determining the equivalent thickness of the masonry for use in Table 721.3.2. |
Exception: For an exterior wall with a fire separation distance greater than 5 feet (1524 mm) the fire shall be assumed to occur on the interior side only.
721.2.2 Concrete floor and roof slabs. Reinforced and prestressed floors and roofs shall comply with Section 721.2.2.1. Multicourse floors and roofs shall comply with Sections 721.2.2.2 and 721.2.2.3, respectively.
TABLE 721.2.2.1 MINIMUM SLAB THICKNESS (inches)
CONCRETE TYPE | FIRE-RESISTANCE RATING (hour) | ||||
1 | 11/2 | 2 | 3 | 4 | |
Siliceous | 3.5 | 4.3 | 5.0 | 6.2 | 7.0 |
Carbonate | 3.2 | 4.0 | 4.6 | 5.7 | 6.6 |
Sand-lightweight | 2.7 | 3.3 | 3.8 | 4.6 | 5.4 |
Lightweight | 2.5 | 3.1 | 3.6 | 4.4 | 5.1 |
For SI: 1 inch = 25.4 mm. |
For SI: 1 inch = 25.4 mm. |
FIGURE 721.2.2.1.2 DETERMINATION OF SLAB THICKNESS FOR SLOPING SOFFITS
For s > 4t, the thickness to be used shall be t
For s <= 2t, the thickness to be used shall be te
For 4t > s> 2t, the thickness to be used shall be
Click to view image | (Equation 7-5) |
where:
s = Spacing of ribs or undulations.
t = Minimum thickness.
te = Equivalent thickness of the slab calculated as the net area of the slab divided by the width, in which the maximum thickness used in the calculation shall not exceed 2t.
For SI: 1 inch = 25.4 mm. |
FIGURE 721.2.2.1.3 SLABS WITH RIBBED OR UNDULATING SOFFITS
For SI: 1 inch = 25.4 mm. |
FIGURE 721.2.2.2 FIRE-RESISTANCE RATINGS FOR TWO-COURSE CONCRETE FLOORS
For SI: 1 inch = 25.4 mm. |
FIGURE 721.2.2.3(1) FIRE-RESISTANCE RATINGS FOR CONCRETE ROOF ASSEMBLIES
For SI: 1 inch = 25.4 mm. |
FIGURE 721.2.2.3(2) FIRE-RESISTANCE RATINGS FOR CONCRETE ROOF ASSEMBLIES
721.2.3 Concrete cover over reinforcement. The minimum thickness of concrete cover over reinforcement in concrete slabs, reinforced beams and prestressed beams shall comply with this section.
TABLE 721.2.3(1) COVER THICKNESS FOR REINFORCED CONCRETE FLOOR OR ROOF SLABS (inches)
CONCRETE AGGREGATE TYPE | FIRE-RESISTANCE RATING (hours) | |||||||||
Restrained | Unrestrained | |||||||||
1 | 11/2 | 2 | 3 | 4 | 1 | 11/2 | 2 | 3 | 4 | |
Siliceous | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 1 | 11/4 | 15/8 |
Carbonate | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 11/4 | 11/4 |
Sand-lightweight or lightweight | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 11/4 | 11/4 |
For SI: 1 inch = 25.4 mm. |
TABLE 721.2.3(2) COVER THICKNESS FOR PRESTRESSED CONCRETE FLOOR OR ROOF SLABS (inches)
CONCRETE AGGREGATE TYPE | FIRE-RESISTANCE RATING (hours) | |||||||||
Restrained | Unrestrained | |||||||||
1 | 11/2 | 2 | 3 | 4 | 1 | 11/2 | 2 | 3 | 4 | |
Siliceous | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 11/8 | 11/2 | 13/4 | 23/8 | 23/4 |
Carbonate | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 1 | 13/8 | 15/8 | 21/8 | 21/4 |
Sand-lightweight or lightweight | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | 1 | 13/8 | 11/2 | 2 | 21/4 |
For SI: 1 inch = 25.4 mm. |
TABLE 721.2.3(3) MINIMUM COVER FOR MAIN REINFORCING BARS OF REINFORCED CONCRETE BEAMSc (APPLICABLE TO ALL TYPES OF STRUCTURAL CONCRETE)
RESTRAINED OR UNRESTRAINEDa | BEAM WIDTHb (inches) | FIRE-RESISTANCE RATING (hours) | ||||
1 | 11/2 | 2 | 3 | 4 | ||
Restrained | 5 | 3/4 | 3/4 | 3/4 | 1a | 11/4a |
7 | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | |
>= 10 | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | |
Unrestrained | 5 | 3/4 | 1 | 11/4 | - | - |
7 | 3/4 | 3/4 | 3/4 | 13/4 | 3 | |
>= 10 | 3/4 | 3/4 | 3/4 | 1 | 13/4 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. |
a. Tabulated values for restrained assemblies apply to beams spaced more than 4 feet on center. For restrained beams spaced 4 feet or less on center, minimum cover of 3/4 inch is adequate for ratings of 4 hours or less. |
b. For beam widths between the tabulated values, the minimum cover thickness can be determined by direct interpolation. |
c. The cover for an individual reinforcing bar is the minimum thickness of concrete between the surface of the bar and the fire-exposed surface of the beam. For beams in which several bars are used, the cover for corner bars used in the calculation shall be reduced to one-half of the actual value. The cover for an individual bar must be not less than one-half of the value given in Table 721.2.3(3) nor less than 3/4 inch. |
TABLE 721.2.3(4) MINIMUM COVER FOR PRESTRESSED CONCRETE BEAMS 8 INCHES OR GREATER IN WIDTH
RESTRAINED OR UNRESTRAINEDa | CONCRETE AGGREGATE TYPE | BEAM WIDTHb (inches) | FIRE-RESISTANCE RATING (hours) | ||||
1 | 11/2 | 2 | 3 | 4 | |||
Restrained | Carbonate or siliceous | 8 | 11/2 | 11/2 | 11/2 | 13/4a | 21/2a |
Carbonate or siliceous | >= 12 | 11/2 | 11/2 | 11/2 | 11/2 | 17/8a | |
Sand lightweight | 8 | 11/2 | 11/2 | 11/2 | 11/2 | 2a | |
Sand lightweight | >= 12 | 11/2 | 11/2 | 11/2 | 11/2 | 15/8a | |
Unrestrained | Carbonate or siliceous | 8 | 11/2 | 13/4 | 21/2 | 5c | - |
Carbonate or siliceous | >= 12 | 11/2 | 11/2 | 17/8a | 21/2 | 3 | |
Sand lightweight | 8 | 11/2 | 11/2 | 2 | 31/4 | - | |
Sand lightweight | >= 12 | 11/2 | 11/2 | 15/8 | 2 | 21/2 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. |
a. Tabulated values for restrained assemblies apply to beams spaced more than 4 feet on center. For restrained beams spaced 4 feet or less on center, minimum cover of 3/4 inch is adequate for 4-hour ratings or less. |
b. For beam widths between 8 inches and 12 inches, minimum cover thickness can be determined by direct interpolation. c. Not practical for 8-inch-wide beam but shown for purposes of interpolation. |
TABLE 721.2.3(5) MINIMUM COVER FOR PRESTRESSED CONCRETE BEAMS OF ALL WIDTHS
RESTRAINED OR UNRESTRAINEDa | CONCRETE AGGREGATE TYPE | BEAM AREAb A (square inches) | FIRE-RESISTANCE RATING (hours) | ||||
1 | 11/2 | 2 | 3 | 4 | |||
Restrained | All | 40 <= A <= 150 | 11/2 | 11/2 | 2 | 21/2 | - |
Carbonate or | 150 < A <= 300 | 11/2 | 11/2 | 11/2 | 13/4 | 21/2 | |
siliceous | 300 < A | 11/2 | 11/2 | 11/2 | 11/2 | 2 | |
Sand lightweight | 150 < A | 11/2 | 11/2 | 11/2 | 11/2 | 2 | |
Unrestrained | All | 40 <= A <= 150 | 2 | 21/2 | - | - | - |
Carbonate or siliceous | 150 < A <= 300 | 11/2 | 13/4 | 21/2 | - | - | |
300 < A | 11/2 | 11/2 | 2 | 3c | 4c | ||
Sand lightweight | 150 < A | 11/2 | 11/2 | 2 | 3c | 4c |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square inch = 645 mm2. |
a. Tabulated values for restrained assemblies apply to beams spaced more than 4 feet on center. For restrained beams spaced 4 feet or less on center, minimum cover of 3/4 inch is adequate for 4-hour ratings or less. |
b. The cross-sectional area of a stem is permitted to include a portion of the area in the flange, provided the width of the flange used in the calculation does not exceed three times the average width of the stem. |
c. U-shaped or hooped stirrups spaced not to exceed the depth of the member and having a minimum cover of 1 inch shall be provided. |
721.2.4 Concrete columns. Concrete columns shall comply with this section.
TABLE 721.2.4 MINIMUM DIMENSION OF CONCRETE COLUMNS (inches)
TYPES OF CONCRETE | FIRE-RESISTANCE RATING (hours) | ||||
1 | 11/2 | 2a | 3a | 4b | |
Siliceous | 8 | 9 | 10 | 12 | 14 |
Carbonate | 8 | 9 | 10 | 11 | 12 |
Sand-lightweight | 8 | 81/2 | 9 | 101/2 | 12 |
For SI: 1 inch = 25 mm. |
a. The minimum dimension is permitted to be reduced to 8 inches for rectangular columns with two parallel sides at least 36 inches in length. |
b. The minimum dimension is permitted to be reduced to 10 inches for rectangular columns with two parallel sides at least 36 inches in length. |
The hook extension at the free end of ties and spirals shall be the larger of six bar diameters and the extension required by Section 7.1.3 of ACI 318. Hooks shall project into the core of the column.
Where openings in the wall are not protected as required by Section 715.4, the minimum dimension of columns required to have a fire-resistance rating of 3 hours or less shall be 8 inches (203 mm), and 10 inches (254 mm) for columns required to have a fire-resistance rating of 4 hours, regardless of the type of aggregate used in the concrete.