Chapter 7 - Fire and Smoke Protection Features
Section 706 - FIRE WALLS
Subsection 706.4 - Fire-resistance rating
Universal Citation: 780 CMR MA Code of Regs 706.4
Current through Register 1531, September 27, 2024
Fire walls shall have a fire-resistance rating of not less than that required by Table 706.4.
TABLE 706.4 FIRE WALL FIRE-RESISTANCE RATINGS
GROUP | FIRE-RESISTANCE RATING (hours) |
A, B, E, H-4, I, R-1, R-2, U | 3a |
F-1, H-3b, H-5, M, S-1 | 3 |
H-1, H-2 | 4b |
F-2, S-2, R-3, R-4 | 2 |
a. In Type II or V construction, walls shall be permitted to have a 2-hour fire-resistance rating. |
b. For Group H-1, H-2 or H-3 buildings, also see Sections 415.4 and 415.5. |
Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.