Current through Register 1531, September 27, 2024
The provisions of 780 CMR 51.00 shall be known as the
Massachusetts Residential Code and are comprised of the International
Residential Code 2009 (IRC) with Massachusetts amendments. The Massachusetts
amendments to the IRC are:
R101.1
Replace as follows:
R101.1
Title.
The Board of Building Regulations and Standards (BBRS) hereby adopts and
incorporates by reference herein the
International Residential Code for
One- and Two-family Dwellings 2009 (IRC). The IRC together with
modifications as set forth herein shall collectively comprise the Eighth
Edition Massachusetts Residential Code for One- and Two-family Dwellings
hereinafter referred to as "this code."
R101.1.1 Add subsection:
R101.1.1
Appendices and Appended
Regulations. In adopting the IRC, BBRS does not adopt Appendices A
through F or N through Q, but does adopt IRC Appendices G through M as modified
herein. BBRS also incorporates into this code the unique Massachusetts
regulations 110.R1 trough 110.R7 of the Eighth Edition of the MA State Building
Code (780 CMR).
R101.2 Add a first sentence as follows:
This code shall be the building code for all towns, cities,
state agencies or authorities in accordance with M.G.L. c. 143, §
94.
R102.2 Replace as
follows:
R102.2
Other Laws.
Massachusetts General Laws (M.G.L.) and the Code of Massachusetts Regulations
(CMR) are often referenced in this code. It is the code user's responsibility
to determine all applicable laws and regulations relevant to sections in this
code.
R102.2.1 Add subsection:
R102.2.1
DDS Facilities.
Additional building features required by the Massachusetts Department of
Developmental Services (DDS) do not change the classification of residences
operated or licensed by DDS as dwellings subject to this
code.
R102.2.2 Add
subsection:
R102.2.2
Municipal Bylaws or
Ordinances. When provisions of this code conflict with municipal bylaws
and ordinances, this code shall govern unless the bylaws or ordinances were
promulgated in accordance with M.G.L. c. 143, § 98.
R102.4 After the word
"codes" in the first sentence, add the following: ", regulations,"
R102.4.1 Add the following subsections:
R102.4.1
Specialized Codes.
Referenced codes include the
specialized codes of M.G.L. c.
143, § 96 and other codes and regulations listed in R102.4.2 through
R102.4.12. The
specialized codes are hereby incorporated into
this code. Other codes and regulations shall be considered part of this code to
the prescribed extent of each such reference.
Note 1. Work regulated by the specialized
codes shall be designed, installed and inspected by individuals
authorized to do so in accordance with the specialized codes.
However, the impact of work regulated by the specialized codes
and other codes and regulations on work governed by this code shall be subject
to inspection by the building official.
Note 2. Work regulated by the Architectural Access
Board regulations (521 CMR) shall be enforced by the building
official. See M.G.L. c. 22, § 13A.
Note 3. Work regulated by the Board of Sheet Metal
Regulations shall be enforced by the building official.
See M.G.L. c. 13, § 102.
R102.4.2
Gas and Fossil Fuel Burning
Appliances. Reference to the International Fuel Gas
Code shall be considered reference to the Massachusetts Fuel Gas and
Plumbing Code (248 CMR). Gas fired appliances are governed by the Massachusetts
Fuel Gas and Plumbing Code. Oil fired appliances are governed by the Board of
Fire Prevention Regulations (527 CMR).
R102.4.3
Mechanical. The
provisions of the International Mechanical Code shall apply to
the installation, alterations, repairs and replacement of mechanical systems,
including equipment, appliances, fixtures, fittings and/or appurtenances,
including ventilating, heating, cooling, air-conditioning and refrigeration
systems, incinerators and other energy-related systems.
R102.4.4
Plumbing. Reference to
the International Plumbing Code shall be considered reference
to the Massachusetts Fuel Gas and Plumbing Code (248 CMR). For sewerage
disposal or water connections also see310 CMR 15.00:
The State Environmental Code, Title 5: Standard Requirements for the
Siting, Construction, Inspection, Upgrade and Expansion of On-site Sewage
Treatment and Disposal Systems and for the Transport and Disposal of
Septage and
314 CMR 3.00: Surface
Water Discharge Permit Program, 5.00: Ground Water Discharge
Permit Program and 20.00: Reclaimed Water Permit Program and
Standards.
R102.4.5
Property Maintenance. Reference to the International
Property Maintenance Code shall be considered reference to this code,
the specialized codes of M.G.L. c. 143, § 96, and
105 CMR 410.000:
Minimum Standards of Fitness for Human Habitation (State Sanitary Code,
Chapter II).
R102.4.6
Fire Prevention. Reference to the
International Fire
Code (IFC) or
International Mechanical Code (IMC) for
fire prevention issues shall be considered reference to the Board of Fire
Prevention Regulations (527 CMR). If 527 CMR does not address an issue covered
by the IFC or IMC, then that said reference code shall apply. If a conflict
regarding fire prevention requirements exists between 527 CMR and 780 CMR the
more stringent standard shall apply.
Note: Building code requirements in the IFC and
IMC are made a part of 780 CMR and are enforceable by the building
official.
R102.4.7
Energy. The provisions of Chapter 11 and/or the
International Energy Conservation Code (IECC) shall apply to
all matters governing the design and construction of buildings for energy
efficiency. See Chapter 11 for guidance.
R101.4.8
Architectural Access.
See the Architectural Access Board regulations at 521
CMR.
R102.4.9
Environmental
Protection. See the Department of Environmental
Protection regulations at 310 CMR and the Division of Water Pollution Control
regulations at 314 CMR.
R101.4.10
Elevators. See the Massachusetts Board of
Elevator Regulations at 524 CMR.
R102.4.11
Electrical. Reference
to the International Electrical Code shall be considered
reference to
527
CMR 12.00: Massachusetts Electrical Code
(Amendments).
R102.4.12
Sheet Metal. See the Board of Examiners of Sheet
Metal Workers regulations at 271 CMR.
R102.5 Delete subsection.
R102.7 Delete the following phrase:
"the International Property Maintenance Code
or the International Fire Code,"
R102.7.2 Add subsection:
R102.7.2
Laws in Effect. Unless
specifically provided otherwise in this code, and narrow to the provisions of
this code, any existing building or structure shall meet and shall be presumed
to meet the provisions of the applicable laws, codes, rules or regulations,
bylaws or ordinances in effect at the time such building or structure was
constructed or altered and shall be allowed to continue to be occupied pursuant
to its use and occupancy, provided that the building or structure shall be
maintained by the owner in accordance with this code.
R102.7.3 Add subsection:
R102.7.3.
Laws Not in Existence.
In cases where applicable codes, rules or regulations, bylaws or ordinances
were not in existence at the time of such construction or alteration, the
building or structure shall be maintained by the owner in accordance with this
code.
R102.7.4 Add
subsection:
R102.7.4.
Less
Stringent. In cases where the provisions of this code are less stringent
than the applicable codes, rules or regulations, bylaws or ordinances in effect
at the time of such construction or substantial alteration, the applicable
provisions of this code shall apply, provided that such application of these
provisions can be reasonably demonstrated to not result in danger to the
public, as determined by the building
official.
R103 Replace entire section R103 as follows:
R103.1
Municipal and State
Enforcement. This code shall be enforced, and enforcement officials
shall be appointed, in accordance with M.G.L. c. 143, §§ 3 and 3A and
M.G.L. c. 22. Reference to The Department of Building Safety shall be
considered reference to the building official.
R103.2 Add the following to this subsection:
#9. EV Ready Space locations per
R404.2.
10. Solar-ready Zone in
accordance with Appendix RA
R104.1 Replace as follows:
R104.1
General. The
building official is hereby authorized and directed to enforce
the provisions of this code in accordance with M.G.L. c. 143.
R104.4.1 Add subsection:
R104.4.1
Coordination of
Inspections. Whenever in the enforcement of this code, or another code
or ordinance, the responsibility of more than one enforcement official of the
jurisdiction is involved, it shall be the duty of the enforcement officials
involved to coordinate their inspections and administrative orders as fully as
practicable so that the owners and occupants of the building or structure shall
not be subjected to visits by numerous inspectors or multiple or conflicting
orders. Whenever an enforcement official observes an apparent or actual
violation not within the official's authority, the official shall report the
findings to the official having jurisdiction.
R104.8 Replace as
follows:
R104.8
Liability. All
claims of liability relative to building officials shall be
governed by M.G.L. c. 258.
R104.10 Replace the last sentence with the
following two sentences:
The details of action granting modifications shall be recorded
and entered in the files of the building official and a copy
forwarded to the BBRS within seven days. A building official
may seek assistance from the district's State building inspector for
modifications.
R104.10.1 Replace as
follows:
R104.10.1
Areas Prone to
Flooding. The building official shall not grant
modifications to any provision related to areas prone to flooding as
established by this code without the granting of a variance to such provisions
by the building code appeals board. Also, no variance to requirements of this
code can be solely utilized to argue for lawful construction/reconstruction
where such construction/reconstruction would conflict with requirements of
M.G.L. c. 131, § 40: Removal, Fill, Dredging or Altering of Land
Bordering Waters (the Wetlands Protection Act), and/or 310 CMR and 314
CMR, as applicable.
R104.10.2 Add subsection:
R104.10.2
Matters Not Provided
For. In recognition of the inherent difficulty of drafting a functional
code that contemplates every situation that may arise in the area of building
safety, this section provides the building official, the
building code appeals board, or the BBRS itself, with reasonable discretion to
ensure that all life safety issues that may arise in the enforcement of this
code may be appropriately addressed. Matters not specifically provided for in
this code regarding structural, egress, fire, energy, sanitary or other
requirements essential to occupant safety shall be determined by the
building official or, in the case of an appeal, the building
code appeals board. If this provision is used, the building
official shall notify the BBRS in writing within seven days of such
determination. For highly specialized buildings and structures that conform to
unique code requirements or nationally recognized standards not required in
this code, registered design professionals shall provide
sufficient information to the building official to support
their approval.
R105.1 Replace as follows:
R105.1
Required. It shall be
unlawful to construct, reconstruct, alter, repair, remove or demolish a
building or structure; or to change the use or occupancy of a building or
structure; or to install or alter any equipment for which provision is made or
the installation of which is regulated by this code without first filing a
written application with the building official and obtaining
the required permit.
R105.2 Replace as follows:
R105.2
Work Exempt from Permit.
Except for activities which may require a
permit pursuant to
other laws, by-laws, rules and the
specialized codes, a
building
permit is not required for the following activities:
Building:
1. One-story detached accessory
structures used as tool and storage sheds, playhouses and similar
uses, but not garages, provided the floor area does not exceed 200 square feet
(18.58 m2)
2. Fences not over six feet (1829 mm)
high.
3. Retaining walls that are
not over four feet (1219 mm) in height measured from the bottom of the footing
to the top of the wall, unless supporting a surcharge, or that retain over four
feet of unbalanced fill.
4.
Sidewalks and driveways.
5.
Painting, papering, tiling, carpeting, cabinets, counter tops and similar
finish work.
6. Prefabricated
swimming pools that are less than 24 inches (610 mm) deep.
7. Swings and other playground
equipment.
8. Window awnings
supported by an exterior wall which do not project more than 54 inches (1372
mm) from the exterior wall and do not require additional support.
9. Decks not exceeding 200 square feet (18.58
m2) in area, that are not more than 30 inches (762
mm) above grade at any point, are not attached to a
dwelling and do not serve the exit door required by subsection
R311.4.
R105.2.1 Add the following
note:
Note: Pursuant to the terms of the specialized
codes of M.G.L. c. 143, § 96, this exemption might not apply to emergency
repairs conducted under those specialized codes.
R105.2.2 Replace as follows:
R105.2.2
Ordinary Repairs. A
building permit is not required for ordinary
repairs.
R105.2.3 Delete subsection.
R105.3 Replace items 3.
and 4. as follows:
3. Indicate the use and
occupancy for which the proposed work is intended. If the work involves a care
facility or residence licensed by a State agency, indicate the agency name and
appropriate licensing regulation on the permit.
4. Be accompanied by construction
documents and other information as required in Subsection R106.1.
Construction documents shall list any building features
required by a Massachusetts agency for licensed care facilities that are beyond
the requirements of this code. Any additional building features required by the
Massachusetts Department of Developmental Services shall not result in a change
in the classification of a DDS operated or licensed residences for five or
fewer occupants and their compliance with this code.
R105.3.1.1 Replace as follows:
R105.3.1.1
Determination of
Substantially Improved or Substantially Damaged Existing Buildings in Flood
Hazard Areas and Coastal Dunes. For applications for reconstruction,
rehabilitation, addition or other improvement of existing buildings or
structures located in an area prone to flooding as established by Table
R301.2(1),
the building official shall examine or cause to be
examined the
construction documents and shall prepare a
finding with regard to the value of the proposed work. For buildings that have
sustained damage of any origin, the value of the proposed work shall include
the cost to repair the building or structure to its predamaged condition.
In determining the value of the proposed work, the
building official shall consider the following:
A substantial improvement means any repair, reconstruction,
rehabilitation, addition or improvement of a building or structure, the cost of
which equals or exceeds 50% of the market value of the building or structure
before the improvement or repair is started. If the building or structure has
sustained substantial damage, all repairs are considered substantial
improvement regardless of the actual repair work performed. The term does not
include:
1. Improvements of a building
or structure required to correct existing health, sanitary or safety code
violations identified by the building official and which are
the minimum necessary to assure safe living conditions; or
2. Any alteration of an historic building or
structure, provided that the alteration will not preclude the continued
designation as an historic building or structure. For the purpose of this
exclusion, an historic building is:
2.1.
Listed or preliminarily determined to be eligible for listing in the National
Register of Historic Places; or
2.2. Determined by the Secretary of the U.S.
Department of Interior as contributing to the historical significance of a
registered historic district or a district preliminarily determined to qualify
as an historic district; or
2.3.
Designated as historic under a state or local historic preservation program
that is approved by the Department of Interior.
If the building official finds that the value
of proposed work equals or exceeds 50% of the market value of the building or
structure before the damage has occurred or the improvement is started, the
building official shall determine it to be substantial damage
or substantial improvement.
Applications determined by the building
official to constitute substantial improvement or substantial damage
shall require all existing portions of the entire building or structure to meet
the requirements of Section R322.
R105.3.1.1.1 Add subsection:
R105.3.1.1.1
Determination of
Substantial Repair of a Foundation. When work to repair or replace a
foundation results in the repair or replacement of a portion of the foundation
with a perimeter along the base of the foundation that equals or exceeds 50% of
the perimeter of the base of the foundation measured in linear feet the
building official shall determine it to be substantial repair
of a foundation. Applications determined by the building
official to constitute substantial repair of a foundation shall
require all existing portions of the entire building or structure to meet the
requirements of Section R322.
R105.3.1.2 Add subsection:
R105.3.1.2
Other Requirements.
The following requirements must be satisfied before a building
permit is issued:
Zoning: in accordance with M.G.L. c. 40A or St.
1956, c. 665.
Railroad Right-of-way: in accordance with M.G.L.
c. 40, § 54A.
Water Supply: in accordance with M.G.L. c. 40,
§ 54; also refer to
310 CMR
22.00:
Drinking Water and/or
310 CMR 36.00:
Massachusetts Water Resources Management Program, when
applicable.
Wastewater: in accordance with 310 CMR 15.00:
The State Environmental Code, Title 5: Standard Requirements for the
Siting, Construction, Inspection, Upgrade and Expansion of On-site Sewage
Treatment and Disposal Systems and for the Transport and Disposal of
Septage and
314 CMR 3.00: Surface
Water Discharge Permit Program, 5.00: Ground Water Discharge
Permit Program 7.00: Sewer System Extension and Connection
Permit Program, and 20.00: Reclaimed Water Permit Program and
Standards
Debris Removal: in accordance with M.G.L. c. 40,
§ 54 and M.G.L. c. 111, § 150A; also refer to DEP Regulations
310 CMR
7.09(2) and
310 CMR 7.15, when
applicable.
Workers Compensation Insurance: in accordance with
M.G.L. c. 152, § 25C(6).
Hazards to Air Navigation: in accordance with
M.G.L. c. 90, § 35B.
Construction in Coastal Dunes: in accordance with
M.G.L. c. 131, § 40 and the Coastal Wetland regulations at
310 CMR 10.21
through
10.35.
R105.7 After the word "work"
insert the phrase "and be posted conspicuously"
R105.8.1 Add subsection:
R105.8.1
Workmanship. All work
shall be conducted, installed, protected and completed in a workmanlike and
acceptable manner so as to secure the results intended by this
code.
R106.1 At the end
of the first paragraph add the following:
All plans and specifications for work designed by a
registered design professional shall bear the seal and
signature of the responsible registered design professional in
accordance with M.G.L. c. 143, § 54A. See also
www.mass.gov/dpl for policy on
electronic seal and signature for certain registered design
professionals.
R106.3.3.4 Add
Subsection:
R106.3.3.4
Fire Department
Review. For permits that include fire protection system
work, construction documents shall be filed simultaneously
with the head of the local fire department and building
official for review and approval. The fire department shall complete
its review within ten-working days after receiving the documents. Upon the fire
department's request, the building official may grant one or
more extensions up to a total review period maximum of 30-days. If the fire
department review is not received within the allowed time frame the
building official may upon review deem the documents in
compliance. If the head of the local fire department disapproves such
construction documents, he or she shall notify the
building official (refer to M.G.L. c. 148, § 28A) in
writing citing relevant sections of noncompliance with this code or the section
of the referenced standards of Chapter 44.
R106.5 Replace as follows:
R106.5
Retention of Construction
Documents. Sets of approved construction documents
shall be retained by the building official in accordance with
M.G.L. c. 66, § 8.
R107.1 Add this last sentence:
Prior to issuing a certificate, the building
official shall consult with the head of the fire department.
R107.3 Replace as follows:
R107.3
Temporary Power.
See527
CMR 12.00: Massachusetts Electrical Code
(Amendments).
R108.3 Replace as follows:
R108.3
Building Permit
Valuations. The applicant for a permit shall provide an
estimated permit value at time of application. If, in the
opinion of the building official the valuation is
underestimated on the application, the permit shall be denied,
unless the applicant can provide detailed estimates acceptable to the
building official. Final building permit
valuation shall be set by the building official.
108.5 Delete this
subsection.
108.6 Replace as
follows:
108.6
Work Commencing Before
Building Permit Issued. Any person who commences any work on a building
or structure governed by this code before obtaining the necessary building
permit shall be in violation of this code and subject to
penalties. See Section 114.
R109.1 At the end of this subsection add the
following:
It shall be the duty of the permit holder to
provide access to and means for inspections of work required by this code. The
building official may require the permit
holder or his representative to attend these inspections.
R109.1.2 At the end of the sentence add the
following and delete the exception: 'and as otherwise required by the
specialized codes'.
R109.1.3 After the word "flooding" add "and
coastal dunes".
R109.1.5 Add a
second sentence as follows:
The building official shall inform the
applicant of the required points of inspection at the time of the
permit application.
R110.1 Add a last sentence as follows:
Conformance is required to all applicable specialized
codes and when applicable,
310 CMR
7.00: Air Pollution, 310 CMR 15.00:
The State Environmental Code, Title 5: Standard Requirements for the
Siting, Construction, Inspection, Upgrade and Expansion of On-site Sewage
Treatment and Disposal Systems and for the Transport and Disposal of
Septage,
310 CMR
22.00: Drinking Water or 310 CMR
30.000: Hazardous Waste, prior to the issuance of the
certificate of occupancy.
R110.2 Replace as follows:
R110.2
Altered Buildings or
Structures. A building or structure, in whole or in part, altered to
change from one use group to another; to a different use within the same use
group; the maximum live load capacity; or the occupancy load capacity shall not
be occupied or used until a certificate has been issued certifying that the
work has been completed in accordance with the provisions of the approved
permits and applicable codes.
R110.2.1 Add subsection:
R110.2.1
Massachusetts' Licensed Care
Facilities. Certificate of Occupancy inspections for Massachusetts
licensed care facilities, including inspection of special building features
required by the licensing agency, shall be limited to verifying compliance with
the provisions of this code.
R110.3 Add an item 10. as follows:
10. If a care facility is licensed by a State
agency, then the name of the agency and the name and number of any relevant
Code of Massachusetts Regulations (CMR) that apply regarding building features
and a list of those building features above and beyond those required by this
code.
R111 Delete this
section.
112.1 Replace as follows:
112.1
General. Appeals of
orders, decisions, determinations and failures to act made by any state or
local agency or any person or state or local agency charged with the
administration or enforcement of the state building code or any of its rules
and regulations, except the
specialized codes, relative to the
application and interpretation of this code shall be addressed by the building
code appeals board in accordance with M.G.L. c. 143, § 100.
R112.2.1 Delete subsection.
R112.2.2 Delete subsection.
R112.3 Replace as
follows:
R112.3
Qualifications.
See M.G.L. c. 143, § 100, and 780 CMR
113.
R112.4 Replace as
follows:
R112.4
Administration.
See M.G.L. c. 143, § 100, and 780 CMR
113.
R113.1 After the
words "demolish or" add the following phrase "change the use or"
R113.2 After the words "demolition or" add
the following phrase "change the use or"
113.2.1 Add subsection:
113.2.1
Notice Issuance. Every
notice or order shall be in writing and shall be served on the person
responsible:
1. Personally, by any person
authorized by the building official; or
2. By any person authorized to serve civil
process by leaving a copy of the order or notice at the responsible party's
last and usual place of business or abode; or
3. By sending the party responsible or their
agent authorized to accept service of process in the Massachusetts a copy of
the order by registered or certified mail return receipt requested, if he is
within the Massachusetts; or
4. If
the responsible party's last and usual place of business or abode is unknown,
by posting a copy of this order or notice in a conspicuous place on or about
the premises in violation and by publishing it for at least three out of five
consecutive days in one or more newspapers of general circulation wherein the
building or premises affected is situated.
113.3 Replace as follows:
113.3
Enforcement. Violations to
this code shall be enforced in accordance with the applicable provisions of
M.G.L. c. 143, §§ 6 through 10 and § 94, M.G.L. c. 148, and
M.G.L. c. 148A, and any other applicable state law.
113.4 Insert after the word "alters" the text
", makes a change of use"
R115 Add
section:
SECTION R115
UNSAFE STRUCTURES AND EQUIPMENT
R115.1
General. Unsafe or
dangerous structures are governed by M.G.L. c. 143, §§ 6, 7, 8, 9 and
10.
R202 Add and/or
revise the following defined terms:
Clean Biomass Heating Systems. Wood-pellet fired
central boilers and furnaces where the equipment has a thermal efficiency
rating of 80% (higher heating value) or greater; and a particulate matter
emissions rating of no more than 0.15 lb/MMBtu PM heat output.
Electric Vehicle. An automotive-type vehicle for
on-road use, such as passenger automobiles, buses, trucks, vans, neighborhood
electric vehicles, electric motorcycles, and the like, primarily powered by an
electric motor that draws current from a rechargeable storage battery, fuel
cell, photovoltaic array, or other source of electric current.
Informational Note: defined as in
527
CMR 12.00: Massachusetts Electrical Code
(Amendments) section 625.2.
Electric Vehicle Supply Equipment (EVSE). The
conductors, including the ungrounded, grounded, and equipment grounding
conductors, and the electric vehicle connectors, attachment plugs, and all
other fittings, devices, power outlets, or apparatus installed specifically for
the purpose of transferring energy between the premises wiring and the electric
vehicle.
Informational Note: defined as in
527
CMR 12.00: Massachusetts Electrical Code
(Amendments) section 625.2.
Electric Vehicle Charging Space ("EV Ready
Space"). A designated parking space which is provided with one dedicated
50-ampere branch circuit for EVSE servicing Electric Vehicles.
High Efficiency Lamps. Light-emitting diode (LED)
lamps with an efficiency of not less than the following:
1. 60 lumens per watt for lamps over 40
watts;
2. 50 lumens per watt for
lamps over 15 watts to 40 watts,
3.
45 lumens per watt for lamps 15 watts or less.
R301 Replace the section with the following:
Massachusetts is a Climate Zone 5A
Delete Table R301.1
R303.3 Add two sentences as follows:
Mechanical ventilation is required for bathrooms with a shower
or bathtub. Also see105 CMR 410.000:
Minimum Standards of Fitness for Human Habitation (State Sanitary Code,
Chapter II) and
248
CMR 10.00: Uniform State Plumbing
Code as these codes may also have mechanical ventilation
requirements.
R303.6 Add a
first sentence as follows:
'Stairway illumination shall comply with
527 CMR 10.00: Fire
Prevention, General Provisions.' and retain the remaining text of the
paragraph.
R303.8 Add a last
sentence as follows:
'See105 CMR 410.000:
Minimum Standards of Fitness for Human Habitation (State Sanitary Code,
Chapter II) for rental property.'
R305.1 Delete the text 'and portions of
basements containing these spaces'
R305.1.1
Replace the paragraph as follows:
'Basements areas, including but not limited to areas with
suspended ceilings, shall have a ceiling height of not less than six feet eight
inches.' Retain the Exception.
R306.5 Add subsection:
R306.5
Other Regulations.
Requirements of Section R306 shall be in conformance with the Board of Fire
Prevention Regulations at 527 CMR,
248
CMR 10.00: Uniform State Plumbing
Code, 310 CMR 15.00: The State Environmental Code, Title 5:
Standard Requirements for the Siting, Construction, Inspection, Upgrade and
Expansion of On-site Sewage Treatment and Disposal Systems and for the
Transport and Disposal of Septage and
105 CMR 410.000:
Minimum Standards of Fitness for Human Habitation (State Sanitary Code,
Chapter II).
R307 Replace in its entirety as follows:
R307.1
Toilet, Bath, and Shower.
Requirements of Section R307 shall be in conformance with
248
CMR 10.00: Uniform State Plumbing
Code.
R308.1 Add
a last sentence as follows: 'Also see M.G.L. c. 143
§§ 3t, 3u, and 3v'
R310.1.1 Add a second exception:
Exception. Double hung windows shall have a
minimum net clear opening of 3.3 square feet (0.31
m2).
R310.1.2 Replace as follows:
R310.1.2
Dimensions. The minimum
net clear opening dimensions shall be 20 inches by 24 inches in either
direction.
R311.1
and
R311.2 Replace as follows:
R311.1
Means of Egress. All
dwellings shall be provided
with two means of egress as provided in this section. The means of egress shall
provide a continuous and unobstructed path of vertical and horizontal egress
travel from all portions of the
dwelling to the exterior of
the
dwelling at the required egress doors without requiring
travel through a garage. For townhouses also
see the
Architectural Access Board's regulations at 521 CMR.
Exception. Egress through the secondary egress
door, required in subsection R311.2, may include travel through a garage
provided the garage has an exit door meeting the requirements of a secondary
egress door.
R311.2
Egress Door. At least two
egress doors shall be provided for each dwelling unit, remote
as possible from each other, at the normal level of exit.
Exceptions:
1. In multi-level dwellings, including but
not limited to townhouses, split-level and raised ranch style layouts, the two
separate egress doors required by R311.2 are permitted to be located on
different levels.
2. Where site
topography prevents direct access at two remote locations to grade from the
normal level of entry, the two separate egress doors required by R311.2 are
permitted to be located on different levels.
The primary egress door shall be side-hinged, and shall provide
a minimum clear width of 32 inches (813 mm) when measured between the face of
the door and the stop, with the door open 90 degrees (1.57 rad). The secondary
egress door shall be side-hinged or sliding, and shall provide a minimum clear
width of 28 inches (711mm) when measured between the face of the door and the
stop, with the door open 90 degrees (1.57 rad). The minimum clear height of the
primary and secondary egress door opening shall not be less than 78 inches
(1981 mm) in height measured from the top of the threshold to the bottom of the
stop. Other exterior doors shall not be required to comply with these minimum
dimensions. Egress doors shall be readily openable from inside the
dwelling without the use of a key or special knowledge or
effort.
R311.2.1 Add
subsection:
R311.2.1
Interior
Doors. All doors providing access to habitable rooms shall have a
minimum nominal width of 30 inches (762 mm) and a minimum nominal height of six
feet, six inches (1981 mm).
Exceptions:
1. Doors providing access to bathrooms are
permitted to be 28 inches (711 mm) in nominal width.
2. Doors providing access to bathrooms in
existing buildings are permitted to be 24 inches (610 mm) in nominal width.
R311.7.4.1 Replace the phrase '73/4
inches (196 mm)' with '81/4 inches (210 mm)'.
R311.7.4.2 Replace the phrase '10 inches (254
mm)' with '9 inches (229 mm)'
R311.7.4.2 Replace the second paragraph as
follows:
Winder treads shall have a minimum tread depth equal to the
tread depth of the straight run portion of the stairs measured as above at a
point 12 inches from the side where the treads are narrower. Winder treads
shall have a minimum tread depth of three inches at any point. Within any
flight of stairs, the greatest winder tread depth at the 12 inch walk line
shall not exceed the smallest by more than d inch.
R313.1.1 Replace as follows:
R313.1.1
Design and
Installation. Automatic residential fire sprinkler systems for
townhouses shall be designed and installed in accordance with NFPA 13, 13R, or
13 D, as applicable.
1. A townhouse building
with an aggregate area of 12,000 square feet or more shall use a NFPA 13
system.
2. A townhouse building
with an aggregate area less than 12,000 square feet shall be permitted to use a
NFPA 13-R system.
Exception. A three unit townhouse building with an
aggregate area less than 12,000 square feet shall be permitted to use a NFPA
13-D system.
For the purposes of this section the aggregate area shall be
the combined area of all stories of the building and fire walls shall not be
considered to create separate buildings. Aggregate area shall include garage
area, basement area, and finished attic area. Unfinished attic area shall not
be included in aggregate area.
R313.2 Replace as follows:
R313.2
One- and Two-family Dwellings
Automatic Fire Sprinkler Systems. Only one- and two-family dwellings
having an aggregate area greater than 14,400 square feet shall have fire
sprinklers installed in accordance with NFPA 13D. Aggregate area for the
purpose of this section shall include basements but not garages and unfinished
attics. Additions to such dwellings with automatic sprinkler systems shall have
automatic sprinklers installed in accordance with NFPA 13D.
R313.2.1 Delete the text: 'Section P2904
or'
R314.1
Replace the text "listed in accordance with UL 217" as follows "photoelectric
type smoke alarms listed in accordance with UL 217 or UL 268.
R314.3 Add subsections 4 and 5 as follows:
4. Near the base of all stairs where such
stairs lead to another occupied floor.
5. For each 1,200 square feet of area or part
thereof.
R314.5 Add a
section and a subsection:
R314.5
Heat
Detector. A single heat detector listed for the ambient environment
shall be installed in:
1. Any integral garage
("garage under") or attached garage to the main house (detached garages do not
require a heat detector).
2. A new
addition attached garage to an existing dwelling. If the existing house
contains a fire detection system that is compatible with the garage heat
detector, then the detector shall be interconnected to the existing system.
Where the existing fire detection system is not compatible with the garage heat
detector, the garage heat detector shall be connected to a sounder (occupant
notification appliance) or compatible heat detector containing a sounding
device, located in the dwelling and within 20 feet (6096 mm) of the nearest
door to the garage from the dwelling. The required garage heat detector is
neither required to incorporate audible alarm notification nor is any audible
notification device required in the garage.
R314.5.1
Heat Detector
Placement. For flat-finished ceilings, the single heat detector shall be
placed on or near the center of the garage ceiling. For sloped ceilings having
a rise to run of greater than one foot in eight feet (305 mm in 2438 mm), the
single heat detector shall be placed in the approximate center of the vaulted
ceiling but no closer than four inches (102 mm) to any wall.
R315.1 Replace as
follows:
R315.1
Governing
Regulations. Carbon monoxide alarms (alarms) for new construction and
existing dwellings shall be furnished, installed and maintained by the owner in
accordance with this section, M.G.L. c. 148, § 26F1/2,
527 CMR 31.00: Carbon
Monoxide Alarms, 248 CMR, NFPA 720 and the manufacturer's
instructions.
R315.2
Replace as follows:
R315.2
Installation
Locations. One alarm shall be installed on each story of a dwelling
unit, including basements and cellars (but not including crawl spaces and
uninhabitable attics). When mounting a carbon monoxide alarm on a story with a
bedroom, the alarm, shall be located outside of bedrooms but no further than 10
feet of any bedroom door. If a combination smoke/carbon monoxide alarm is used,
its location must comply with this section.
R315.3 Replace as follows:
R315.3
New Construction. Alarms
shall either be an interconnected 120V or part of a low-voltage combination
system or wireless system. Alarms shall have secondary (standby) power from
monitored batteries in accordance with NFPA 72. For fire alarm control units
(panels) and wireless systems, the panel battery shall serve as the source of
secondary power. Alarms shall be UL 2034 or UL 2075 listed, as applicable.
Alarms may be interconnected with fire alarms providing they are compatible and
the fire alarms take precedence.
R315.4 Add subsection:
R315.4
Existing Dwellings. For
existing dwellings, carbon monoxide alarms shall be provided in accordance with
Section 315 for new construction, as applicable, for the following
circumstances:
1. When one or more bedrooms
are added or created in a dwelling unit, the entire dwelling shall be provided
with alarms.
2. When a dwelling
unit undergoes complete reconstruction such that all walls and ceilings are
open to framing the entire dwelling unit shall be provided with
alarms.
3. In an existing
two-family dwelling, when one or more bedrooms are added or created in both of
the two dwelling units, the entire building shall be provided with
alarms.
4. In a townhouse building
when one or more bedrooms are added or created in a dwelling then that dwelling
unit shall be provided with carbon monoxide alarms.
5. In a townhouse building when a dwelling
unit undergoes complete reconstruction such that all walls and ceilings are
open to framing, that dwelling unit shall be provided with carbon monoxide
alarms.
R319.1
Replace subsection:
R319.1
Address
Numbers. See M.G.L. c. 148, §
59.
R320.1 Replace
subsection:
R320.1
Scope. For
townhouses see 521 CMR.
R321.1 Replace 'ASME A17.1' with '524
CMR'.
R321.2 Replace 'ASME A18.1'
with '524 CMR'.
R321.3 Replace 'ICC
A117.1' with '524 CMR and 521 CMR'.
R322.1 Replace as follows and delete the
exception:
R322.1
General.
Buildings and structures constructed in whole or in part in flood hazard areas
(including A or V Zones) as established in Table R301.2(1), or in a coastal
dune as established in Section R322.4 shall be designed and constructed in
accordance with the provisions contained in this section.
R322.1.1 Add the following note to this
subsection:
Note. In using ASCE 24 delete tables 1-1, 2-1,
4-1, 5-1, 6-1, and 7-1. For elevation requirements use elevation requirements
of R322, as amended. Also, delete references to Coastal A zones and instead use
requirements for A zones in R322.
R322.1.4 Replace as follows:
R322.1.4
Establishing the Design Flood
Elevation. The design flood elevation shall be used to define areas
prone to flooding. The design flood elevation is the base flood elevation at
the depth of peak elevation of flooding (including wave height) which has a 1%
(100-year flood) or greater chance of being equaled or exceeded in any given
year, and as obtained from the community's Flood Insurance Study (FIS) with the
accompanying Flood Insurance Rate Map (FIRM) and Flood Boundary and Floodway
Map (FBFM).
R322.1.4.2 Delete
subsection.
R322.1.5 Replace "is useable" with "is not a
basement and is useable".
R322.1.7
Delete.
R322.1.11 Add subsection:
R322.1.11
Basement. The portion
of a building having its floor subgrade (below ground level) on all sides, but
is not a crawlspace. This definition of "Basement" is limited in application to
the provisions of Section R322.
R322.1.12 Add subsection:
R322.1.12
Construction
documents. The construction documents shall include
documentation that is prepared and sealed by a registered design
professional that the design and methods of construction to be used
meet the applicable criteria of this section.
R322.2 Replace as
follows:
R322.2
Flood Hazard Areas (A
Zones). All areas that have been determined to be prone to flooding but
not subject to high velocity wave action shall be designated as flood hazard
areas. Flood Hazard areas shall include all areas shown as A zones on the most
recent Flood Hazard Boundary Map or Flood Insurance Rate Map. All building and
structures constructed in whole or in part in flood hazard areas shall be
designed and constructed in accordance with subsections R322.2.1 through
R322.2.3.
R322.2.1 Revise as follows and
delete the exception:
R322.2.1
Elevation
Requirements.
1. Buildings and
structures in flood hazard areas shall have the lowest floors elevated to or
above the design flood elevation.
2. In areas of shallow flooding (AO Zones),
buildings and structures shall have the lowest floor (including basement)
elevated at least as high above the highest adjacent grade as the depth number
specified in feet on the FIRM, or at least 2 feet (610 mm) if a depth number is
not specified.
3. Basement floors
shall be elevated to or above the design flood elevation.
4. For lateral additions that are a
substantial improvement, only the addition shall be elevated so that the lowest
floor, including basement/cellars, is located at or above design flood
elevation.
R322.2.2 In the first sentence, after "design
flood elevation" insert "and are not basements".
R322.3 Add a second sentence as follows:
"Coastal high-hazard areas shall include all areas shown as V
zones on the most recent Flood Hazard Boundary Map or Flood Insurance Rate
Map."
R322.3.1 Delete item
2.
R322.3.2 Replace item 1 and add
item 5 as follows:
1. All buildings and
structures erected within coastal high hazard areas shall be elevated so that
the lowest portion of all structural members supporting the lowest floor, with
the exception of mat or raft foundations, piling, pile caps, columns, grade
beams and bracing, is located at or above the design flood elevation plus two
feet.
5. For lateral additions that
are not a substantial improvement, only the addition shall be elevated so that
the bottom of the lowest horizontal structural member of the lowest floor with
the exception of pilings or pile caps is located at an elevation that is at
least two feet above the design flood elevation.
322.3.6 Delete.
R322.4 Add subsection:
R322.4
Coastal Dunes. The
following applies to construction in a coastal wetland resource area:
R322.4.1
Determination of Coastal
Dunes. To reduce flood damage, ensure the structural integrity of
buildings or structures including manufactured homes, located in coastal dunes,
to protect the public safety and to eliminate certain conflicts between the
coastal dune performance standards set forth in the Wetlands Protection Act
Regulations,
310 CMR 10.28, and
this code, R322.4 establishes requirements for design and construction in
coastal dunes significant to the interests of flood control and/or storm damage
prevention identified in
310 CMR 10.28:
Coastal Dunes.
To determine whether a proposed building or structure,
including a manufactured home, a lateral addition, work on a foundation that
under R105.3.1.2 requires compliance with R322, or substantial improvement to a
building or structure that has incurred substantial damage as the result of
flooding and/or storms is located within an area that is a coastal dune
significant to the interests of flood control and/or storm damage prevention,
the building official shall require the submission of certain
construction documents in accordance with R322.4.2.
R322.4.2
Construction
Documents. For buildings and structures, including new or replacement
manufactured homes, lateral additions, foundations that are replaced in total
or repaired so as to constitute substantial repair of a foundation, or
substantial repair or improvement of a building or structure that has incurred
substantial damage as a result of flooding and/or storms, proposed on a parcel
of land that is located wholly or partially within a coastal wetland resource
area shown on the map entitled "Map of Coastal Wetland Resources For Building
Officials", the
building official shall require submission of
one of the
construction documents specified in (a) through (d)
along with a notarized statement by the applicant that the Order, Determination
or Notice is in effect and is not the subject of any administrative appeals
before the Department of Environmental Protection or the Division of
Administrative Law Appeals. No building
permit shall issue
unless and until a construction document that conforms to the requirements of
this section is submitted.
(a) An Order of
Conditions establishing the boundaries of all coastal wetland resource areas in
a plan referenced in and accompanying the Order. The Order shall determine
whether the coastal wetland resource areas are significant to any of the
interests identified in the Wetlands Protection Act, M.G.L. c. 131, § 40
including the interests of flood control and storm damage prevention. If the
Order indicates that the proposed construction work is located within a coastal
dune that is significant to the interests of flood control and/or storm damage
prevention, the Order of Conditions must allow the proposed
construction.
(b) An Order of
Resource Area Delineation stating that the proposed construction work is
outside the boundaries of all coastal wetland resource areas as shown on a plan
referenced in and accompanying the Order.
(c) A Determination of Applicability stating
that the proposed construction work is outside the boundaries of all coastal
wetland resource areas as shown on a plan referenced in and accompanying the
Determination or will not fill, dredge or alter a coastal wetland resource
area.
(d) A Notice of
Non-significance evidencing that the proposed construction work is within a
coastal wetland resource area as shown on a plan referenced in and accompanying
the Notice and stating that the coastal wetland resource area is not
significant to any of the interests identified in M.G.L. c. 131, § 40:
Removal, Fill, Dredging or Altering of Land Bordering Waters
(the Wetlands Protection Act).
R322.4.3
Structural Elevation.
The elevation of the bottom of the lowest horizontal structural member, as
required by the lowest floor elevation inspection in Subsection R109.1.3, shall
be submitted.
R322.4.4
Additional Documentation. Documentation for buildings located in
more than one zone shall meet the requirements of all zones.
R322.4.5
Elevation Requirements.
For new buildings and structures, new foundations, replacement or substantial
repair of a foundation, or repair of a substantially damaged structure where
damage is the result of a storm or flooding the entire structure shall be
elevated so that the bottom of the lowest horizontal structural member of the
lowest floor with the exception of pilings or pile caps is located at the
elevation required by the Order of Conditions of the local Conservation
Commission in accordance with the Wetlands Protection Act, M.G.L. c. 131,
§40: Removal, Fill, Dredging or Altering Land Bordering
Waters (the Wetland Protection Act) and Wetlands Protection
Regulations,
310 CMR 10.21
through
10.35:
Additional Regulations for Coastal Wetlands. For lateral
additions that are not a substantial improvement, only the addition shall be
elevated so that the bottom of the lowest horizontal structural member of the
lowest floor with the exception of pilings or pile caps is located at the
elevation required by the Order of Conditions of the local Conservation
Commission in accordance with M.G.L. c. 131, § 40 and Wetlands Protection
Regulations,
310 CMR 10.21
through
10.35.
R322.4.6
Foundations.
Foundations for work meeting the elevation requirements of Section R322 shall
consist of open pilings without footings to allow the movement of the dune.
Exception. Where surface or subsurface conditions
consist of non-erodible soil that prevents the use of pile foundations, spread
footings or mat foundations may be permitted. Such foundations shall be
anchored to prevent sliding, uplift or overturning of the footing and the
non-erodible soil it is attached to and be designed to withstand any
combination of loads.
R322.4.7
Enclosed Areas below Design
Flood Elevation. Enclosures are not permitted below the lowest
horizontal structural member of the lowest floor.
R401.1 Revise
the section as follows:
R401.1
Scope. This chapter regulates the energy efficiency for the design
and construction of buildings regulated by 780 CMR. Municipalities which have
adopted the Stretch Energy Code shall use the energy efficiency requirements of
780 CMR 110
Appendix AA.
Exception: Temporary structures, as regulated by
Section 3103, do not need to comply with the building envelope requirements of
780 CMR 51.00.
R401.2 Revise the section as follows:
R401.2
Compliance. Projects
shall comply with one of the following:
1.
Prescriptive Path. Sections R401 through R404 and
R407.
2.
Performance
Path. An energy rating index ("ERI") approach, or approved
alternative energy performance rating method in section R406 and the provisions
of sections R401 through R404 indicated as "Mandatory." Qualifying approaches
under R406 include the following:
a. Certified
RESNET HERS rating with Massachusetts amendments.
b. Certified Energy Star Homes, Version
3.1.
c. Certified Passive house
performance method.
R401.3 Add the following to the end of the
paragraph:
The Certificate shall list the final HERS index score when
applicable.
R401.4.1 Insert
after "Table R401.4.1" the text "or 780 CMR Table 1806.2a"
R401.5 Add subsection:
R401.5
Seismic Requirements.
Seismic requirements in this chapter shall only apply to townhouses and shall
not apply to one- and two-family dwellings.
R401.6 Add subsection:
R401.6
Flood Resistant
Construction. See section 322 for flood-resistant
construction requirements.
R402.1.5.1 Add the subsection as follows:
R402.1.5.1
Approved Software for
Prescriptive Path Total UA Alternative: The following software is
approved for demonstrating Total UA compliance:
REScheck-Web or REScheck for Windows Version 4.6.5 or later,
available at http://www.energycodes.gov/rescheck
R402.4.1.1 Amend Table by inserting the
following sentence at the beginning of the column entitled "INSULATION
INSTALLATION CRITERIA" in the row entitled "General requirements":
All insulation shall be installed at Grade I quality in
accordance with ICC/RESNET 301.
R403.1 Add the following to the end of the
second sentence:
"as per subsection R401.2"
R403.1.6 Add the designation "A 307 or other
applicable steel" before the word "anchor bolt" in the first sentence of the
second paragraph. Also, after the words "anchor bolts" insert the text
"installed in accordance with the manufacturer's printed
instructions."
R403.3.3 Replace the
last paragraph with the following:
Post-construction or rough-in testing and verification shall be
done by a HERS Rater, HERS Rating Field Inspector, or an applicable BPI
Certified Professional. A written report of the results of the test shall be
signed by the party conducting the test and provided to the code
official.
R403.6
Replace the section with the following:
R403.6
Mechanical Ventilation (Mandatory). Outdoor air intakes and
exhausts shall have automatic or gravity dampers that close when the
ventilation system is not operating. Each dwelling unit of a residential
building shall be provided with continuously operating exhaust, supply or
balanced mechanical ventilation that has been site verified to meet a minimum
airflow per:
1. R406.3 Equation 4-1:
Ventilation rate, CFM = (0.01 x total square foot area of
house) + [7.5 x (number of bedrooms + 1);
2. Energy Star Homes Version, 3.1.;
3. ASHRAE 62.2-2013; or
4. the following formula for one- and
two-family dwellings and townhouses of three or less stories above grade plane:
Q = .03 x CFA + 7.5 x (Nbr + 1) - 0.052
x Q50 x S x WSF
Where: CFA is the conditioned floor area in
ft2
Nbr is the number of bedrooms
Q50 is the verified blower door air
leakage rate in cfm measured at 50 Pascals
S is the building height factor determined by this
table:
Stories above grade plane
|
1
|
2
|
3
|
S
|
1.00
|
1.32
|
1.55
|
WSF is the shielded weather factor as determined by this
table:
County
|
WSF
|
Barnstable
|
0.6
|
Berkshire
|
0.52
|
Bristol
|
0.54
|
Dukes
|
0.59
|
Essex
|
0.58
|
Franklin
|
0.52
|
Hampden
|
0.49
|
Hampshire
|
0.59
|
Middlesex
|
0.55
|
Nantucket
|
0.61
|
Norfolk
|
0.52
|
Plymouth
|
0.53
|
Suffolk
|
0.66
|
Worcester
|
0.59
|
R403.6.2
through R403.6.6 Add
the following subsections:
R403.6.2
Verification: Installed performance of the mechanical ventilation
system shall be tested and verified by a HERS Rater, HERS Rating Field
Inspector, or an applicable BPI Certified Professional, and measured using a
flow hood, flow grid, or other airflow measuring device in accordance with
either RESNET Standard Chapter 8 or ACCA Standard 5.
R403.6.3
Air-moving Equipment,
Selection and Installation. As referenced in ASHRAE Standard 62.2-2013,
section 7.1, ventilation devices and equipment shall be tested and certified by
Air Movement and Control Association ("AMCA") or Home Ventilating Institute
("HVI") and the certification label shall be found on the product. Installation
of systems or equipment shall be carried out in accordance with manufacturers'
design requirements and installation instructions. Where multiple duct sizes
and/or exterior hoods are standard options, the minimum size shall not be
used.
R403.6.4
Sound
Rating. Sound ratings for fans used for whole building ventilation shall
be rated at a maximum of one sone.
Exception: HVAC air handlers and remote-mounted
fans need not meet sound requirements. There shall be at least four feet of
ductwork between the remote-mounted fan and intake grille.
R403.6.5
Documentation. The
owner and the occupant of the dwelling unit shall be provided with information
on the ventilation design and systems installed, as well as instructions on the
proper operation and maintenance of the ventilation systems. Ventilation
controls shall be labeled with regard to their function, unless the function is
obvious.
R403.6.6
Air Inlets
and Exhausts. All ventilation air inlets shall be located a minimum of
ten feet from vent openings for plumbing drainage systems, appliance vent
outlets, exhaust hood outlets, vehicle exhaust, or other known contamination
sources; and shall not be obstructed by snow, plantings, or any other material.
Outdoor forced air inlets shall be covered with rodent screens having mesh
openings not greater than 1/2 inch. A whole house mechanical ventilation
system shall not extract air from an unconditioned basement unless approved by
a registered design professional. Where wall inlet or exhaust vents are less
than seven feet above finished grade in the area of the venting including, but
not limited to, decks and porches, a metal or plastic identification plate
shall be permanently mounted to the exterior of the building at a minimum
height of eight feet above grade directly in line with the vent terminal. The
sign shall read, in print no less than 1/2 inch in size, "MECH. VENT
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
Exceptions
1. Ventilation air inlets in the wall shall
be separated from dryer exhausts and contamination sources exiting through the
roof by a minimum of three feet.
2.
No minimum separation distance shall be required between local exhaust outlets
in kitchens/bathrooms and windows.
3. Vent terminations that meet the
requirements of the National Fuel Gas Code (NFPA 54/ ANSI
Z223.1) or equivalent.
R404.1.7 Add a last sentence as follows:
Backfill material shall be free draining and free of organic
materials, construction debris, cobbles and boulders, shall be placed in lifts
not exceeding 12-inches and shall be mechanically compacted.
R404.2 Add subsection as follows:
R404.2
Electric Vehicle Charging Spaces
("EV Ready Spaces") Reserved. EV Ready spaces are not required for
detached one- and two-family dwellings and multiple single-family dwellings
(townhouses) not more than three stories above grade plane in height and their
accessory structures not more than three stories above grade place. All other
occupancies otherwise directed to follow the provisions of 780 CMR 51.00:
Massachusetts Residential Code must adhere to any EV
requirements found in 780 CMR 1300.1 (C405.10).
R405 Delete subsection and insert the
following:
R405 Reserved
R406.1 Revise this subsection as follows:
R406.1
Scope. This section
establishes criteria for compliance using an Energy Rating Index ("ERI")
analysis, or approved alternative energy performance rating methods.
R406.1.1
Approved Alternative Energy
Performance Methods. The following rating threshold criteria are
sufficient to demonstrate energy code compliance under R406 without calculation
of a standard reference design. The mandatory provisions of subsection R406.2
also apply:
1.
ENERGY STAR Homes 3.1
Path. New buildings or additions to an existing building, building
system or portion thereof shall be certified to conform to the ENERGY STAR
Certified Homes, Version 3.1 standard.
2.
Passive House Institute US ("PHIUS")
or Passive House Institute ("PHI") Approved Software. Projects
pre-certified through PHIUS or PHI, with a certified Passive House Consultant
or certified Passive House Designer verified "as-built" report demonstrating
compliance with the PHIUS or PHI standard.
3. Any other software approved by the Board
of Building Regulations and Standards.
R406.2 After the last paragraph (on
membranes) add this paragraph:
Through-wall formwork ties shall be removed from both faces of
the foundation walls which enclose basements, cellars, below-grade garages or
any space having the potential to be converted to useable or occupied space.
Remaining holes shall be patched with hydraulic cement.
R406.3 Revise Subsection as follows:
R406.3
Energy Rating Index. The
Energy Rating Index (ERI) shall be determined in accordance with RESNET/ICC
301, the ERI Reference Design Ventilation rate shall be in accordance with
Equation 4-1.
R406.4
Revise the section as follows:
R406.4
ERI-based Compliance. Compliance based on an ERI analysis requires
that the rated design be shown to have an ERI less than or equal to the
appropriate value listed in Table R406.4 when compared to the ERI reference
design for each dwellings unit prior to credit for onsite renewable electric
generation.
Table R406.4.
Maximum Energy Rating Index
Maximum HERS Index
Scorea, b
|
On-site Renewable Energy
Application
|
New Construction
|
Whole House Renovations;
Additions
|
None
|
55
|
65
|
Solar Electric Generation
|
60
|
70
|
Clean Space Heating
|
60
|
70
|
DHW
|
57
|
67
|
Solar Electric and Clean Space Heating
|
65
|
75
|
Solar Electric and DWH
|
62
|
72
|
Solar Electric, Clean Space Heating and DHW
|
67
|
77
|
a Maximum HERS rating prior to
onsite renewable electric generation in accordance with Section R406.4
b Where on-site renewable energy is
included for compliance using the ERI analysis of Section R406.4, the building
shall meet the mandatory requirements of SectionR406.2, and the building
thermal envelope shall be greater than or equal to the levels of efficiency and
SHGC in Table R402.1.2 or Table
R406.4.1 Add the subsection as follows:
R406.4.1
Trade-off for Onsite Renewable
Energy Systems. New construction following R406.3 or existing buildings
and additions following IECC chapter 5 [RE] may use renewable energy trade-offs
to increase the maximum allowable HERS rating for each unit separately served
by any combination of the following:
1.
Solar Generation. Solar photovoltaic array rated at
2.5kW or higher shall offset five HERS points.
2.
Clean Space
Heating. Clean biomass heating system, solar thermal array, cold
climate air source heat pump having rated coefficient of performance (COP) of
at least 1.75 at 5 E F, or geothermal heat pump, or a combination of these
systems, operating as the primary heating system shall offset five HERS
points.
3.
Renewable
Domestic Hot Water Heating (DHW). Solar thermal array or heat pump
for primary domestic hot water heating shall offset two HERS points.
R406.5 Revise the section as follows:
R406.5
Verification by Approved
Agency. Verification of compliance with section R406 shall be completed
by an approved third party. For compliance using a HERS rating or Energy Star
Homes 3.1 certification, verification of compliance shall be completed by the
certified HERS rater. For compliance using PHIUS or PHI, verification of
compliance shall be completed by a certified Passive House
consultant.
R406.6 Revise
this section as follows:
R406.6
Documentation. Documentation of the software used and the
parameters for the residential building shall be in accordance with Sections
R406.6.1 through R406.6.34.
R406.6.1
Compliance Software Tools. If using the ERI or Energy Star Homes
compliance path, software tools used for determining ERI shall be Approved
Software Rating Tools in accordance with RESNET/ICC 301. Where calculations
require input values not specified by Sections R402, R403, R404 and R405, those
input values shall be taken from RESNET/ ICC 301. If using the Passive House
compliance path, software tools for determining Passive House certification
shall be approved software tools by PHIUS or PHI.
R406.6.2
ERI Documentation.
Prior to the issuance if a building permit, the following items must be
provided to the Building Official:
1. A HERS
compliance report which includes a proposed HERS index score of 55 or lower, or
otherwise complies via renewable trade-offs;
2. A description of the unit's energy
features; and
3. A statement that
the rating index score is "based on plans"
Prior to the issuance of a certificate of occupancy, the
following items must be provided to the Building official:
4. A copy of the final certificate indicating
that the HERS rating index score for each unit is verified to be 55 or less or
otherwise complies via renewable trade-offs, together with a completed HERS
rater verified ENERGY STAR Thermal Enclosure System Rater Checklist.
5. A copy of the certificate, as required by
Section R401.3 for each unit listing the final HERS index score of the dwelling
unit.
R406.6.3
ENERGY STAR Homes, Version 3.1 Documentation. Prior to the
issuance of a building permit, the following items(s) must be provided to the
Building Official:
a. A copy of the
preliminary HERS rating, based on plans
b. A description of the unit's energy
features; and
c. A statement that
the rating index score is "based on plans"
Prior to the issuance of a certificate of occupancy, the
following items must be provided to the Building Official:
d. A copy of the final ENERGY STAR Homes
certificate;
e. A copy of the
certified final HERS rating; and
f.
A copy of the signed ENERGY STAR Thermal Enclosure System Rater
Checklist.
g. A copy of the
certificate, as required by Section R401.3 for each unit listing the final HERS
index score of the dwelling unit.
R406.6.4
Passive House
Documentation.
1. If using PHIUS or PHI
Passive House software, prior to the issuance of a building permit, the
following items must be provided to the Building Official:
a. A WUFI or PHPP compliance report which
demonstrates project compliance with PHIUS+2018 (or newer) or PHI performance
requirements;
b. A statement that
the WUFI or PHPP results are "based on plans";
c. Evidence of precertification approval from
PHIUS or PHI.
2. Prior to
the issuance of a certificate of occupancy, the following item(s) must be
provided to the building official:
a. An
updated WUFI or PHPP compliance report which demonstrates project compliance
with PHIUS+2018 (or newer) or PHI performance requirements;
b. A copy of the Passive House Rater's test
results;
c. A statement that the
WUFI or PHPP results are "based on 'as-built' conditions, incorporating the
relevant test results and documented changes to equipment, materials, and
assemblies that impact performance".
R407 Add new section as
follows:
R407
Additional Efficiency
Packages.
R407.1
Requirements
(Prescriptive). Projects shall comply with at least one of the
following:
1. More efficient HVAC performance
in accordance with Section R407.2
2. Heat recovery ventilation (HRV) system or
Energy recovery ventilation (ERV) system in accordance with Section R403.6.1.
The Exception in R403.6.1 shall not be applied if used for compliance with this
Section.
3. High efficiency water
heater or solar thermal hot water heater in accordance with Section
R407.3
R407.2
More
Efficient HVAC Performance. Primary heating equipment shall meet one of
the following efficiency requirements:
1.
Gas, propane or oil-fired furnaces with a minimum AFUE of 95%
2. Gas, propane or oil-fired boilers with a
minimum AFUE of 95%
3. Closed-loop
ground source heat pumps with a minimum COP of 3.5
4. Air-source heat pumps with a minimum HSPF
of 10
R407.3
High
Efficiency Water Heating or Solar Thermal Hot Water Heater. Hot water
heating systems shall meet one of the following:
1. Natural gas or propane water heating with
a minimum Uniform Energy Factor (UEF) of 0.87 or electric heat pump hot water
heater with a minimum UEF of 2.2. On-demand natural gas or propane water
heaters shall not include any buffer tank or hot water storage capacity outside
the water heater itself.
2. A solar
thermal hot water heating system with a minimum of 40 square feet of gross
collection area. The solar hot water heating panels shall have a total solar
resource fraction that is not less than 75%.
R408.7 Delete
the exception.
R502.1.2 Replace the
subsection with the following:
R502.1.2
Existing plus Addition Compliance (Simulated Performance
Alternative). The addition and any alterations that are part of the
project shall comply with Section R406 and shall achieve a maximum HERS index
using Table R406.4.
R502.2.2 At the end of this paragraph add
this text "and no live load acting on the interior span."
R502.3 At the end of the second sentence add
this text:
"or the American Wood Council (AWC) Maximum Span
Calculator for Wood Joists & Rafters found at
http://www.awc.org/calculators/span/calc/timbercalcstyle.asp
"
R502.11.1 Replace
"registered professional" with "registered design professional".
R503.2 Amend the subsection by deleting the
Exception.
Add a new Referenced Standard to Chapter 6 of the IECC as
follows:
DOE U.S. Department of Energy
1000 Independence Ave SW
Washington DC 20585
10 CFR Part 430, Subpart B, Appendix E: Uniform Test Method for
Measuring the Energy Consumption of Water Heaters
R506.1.1 Add subsection, exception, and
associated table:
R506.1.1
Control
Joints. Slabs shall be constructed with control joints having a depth of
at least one quarter of the slab thickness but not less than one inch (25 mm).
Joints shall be spaced at intervals not greater than 30 feet (9144 mm) in each
direction. Control joints shall be placed at locations where the slab width or
length changes.
Exception. Control joints may be omitted when the
slab is reinforced in accordance with Table R506.1.1. Reinforcement shall be
placed at the mid-depth of the slab or two inches (51 mm) from the top of slabs
greater than four inches (102 mm) in thickness.
Table R506.1.1
Maximum Dimension of Slab or Distance Between
Control Joints (ft.)
|
WWF Wire Spacing (in.)
|
WWF Wire Size Designation (in.)
|
Slab Thickness (in.)
|
3.5
|
4
|
4.5
|
5.0
|
5.5
|
6
|
42
|
36
|
32
|
29
|
26
|
24
|
6 x 6
|
W1.4 x W1.4
|
59
|
52
|
46
|
42
|
38
|
35
|
6 x 6
|
W2.0 x W2.0
|
86
|
75
|
67
|
60
|
55
|
50
|
6 x 6
|
W2.9 x W2.9
|
R602.10 Add a second exception as follows:
Exception 2. Unconditioned single story rooms, of areas less
than 600 sq. ft., where the main dwelling is connected to the room via an
exterior door or slider and no other openings between the main dwelling and
room exist (i.e. thermally isolated).
702.3.5.1 Add subsection:
702.3.5.1
Ceiling attachment.
Only designs or methods that use mechanical fasteners in accordance with Table
R702.3.5 shall be used for attaching gypsum board to ceilings in buildings
governed by this code including manufactured buildings. Alternative designs,
such as using adhesive only, are not permitted.
R802.4 Add this text to the end of the second
sentence:
'or utilize the American Wood Council (AWC) Maximum
Span Calculator for Wood Joists & Rafters found at
http://www.awc.org/calculators/span/calc/timbercalcstyle.asp
R802.5 Add this text to the end of
the second sentence:
'or utilize the American Wood Council (AWC) Maximum
Span Calculator for Wood Joists & Rafters found at
http://www.awc.org/calculators/span/calc/timbercalcstyle.asp
R901.1 Add a final sentence as
follows:
In roofing and reroofing, the energy conservation requirements
of Chapter 11 must also be satisfied.
R905.1 Add a final sentence as follows:
Where there is a discrepancy between the requirements of this
section and the manufacturer's printed instructions or code evaluation report,
the manufacturer's printed instructions or code evaluation report shall
govern.
R906.1 Revise the section as
follows:
R906.1
General. The use
of above-deck thermal insulation shall be permitted provided such insulation is
covered with an approved roof covering and complies with FM 4450 or UL 1256. In
roofing and reroofing, the energy conservation requirements of Chapter 11 of
780 CMR 51.00 shall also be satisfied.
R907.1
through R907.5
Reserved
R909.1
through
R909.3 Reserved
Chapter 10:
CHIMNEYS AND FIREPLACES
R1001.1
Revise the section as follows:
R1001.1
General. Masonry fireplaces shall be constructed in accordance
with this section and the applicable provisions of Chapters 3 and 4 of 780 CMR
51.00. Chimneys shall be structurally sound, durable, smoke tight and capable
of conveying flue gases to the exterior safely.
R1003.11 Add a second sentence that reads:
Liner size, length and installation shall be in accordance with
this code or the appliance manufacturer's requirements as applicable.
Chapter 11:
ENERGY
EFFICIENCY
N1100.1 Add the following
sections as follows:
1100.1
Adoption. Buildings shall be designed and constructed in
accordance with the
International Energy Conservation Code -
2018 ("IECC"), as modified by Chapter 11 of 780 CMR 51.00.
Exception: Applications for building permits and
related construction and other documents filed through August 7, 2020 may
comply either with 780 CMR 51.00: Chapter 11, effective
February 7, 2020, or with the versions of those provisions in effect
immediately prior to February 7, 2020, but not a mix of both. After August 8,
2020, concurrency with the prior version of 780 CMR ends, and all applications
for building permits and related construction and other documents shall comply
with 780 CMR effective February 7, 2020 only.
Informational Note: Amendments to the IECC contained
within 780 CMR 51.00 are identified by the letter "R" followed by the
applicable section number.
N1101.2 and
N1101.2.1 Replace as
follows:
N1101.2
Compliance.
Climate zone 5A shall be used for municipalities in MA. Compliance to this
chapter shall be demonstrated by, either:
1.
Meeting the requirements of the International Energy Conservation Code
2009 or,
2. Compliance
with Sections N1101, N1102.4, N1102.5, N1103.1, N1103.2.2, N1103.2.3, and
N1103.3 to N1103.9 and either:
a. Sections
N1102.1 through N1102.3, N1103.2.1 and N1104.1 or
b. Section 405 of the
International
Energy Conservation Code 2009 and these Massachusetts amendments:
405.6.2.1 Add subsection:
405.6.2.1
Approved Calculation Software
Tools. Software tools meeting the requirements of Subsection 405.6 are:
405.7 Add subsections:
405.7
Approved Alternative Energy
Performance Methods. In addition to the IECC performance compliance path
detailed in subsections 405.1 to 405.5 the following rating threshold criteria
of this section are sufficient to demonstrate energy code compliance under
section 405 without calculation of a standard reference design.
1.
RESNET Approved Software for the
Home Energy Rating System (HERS). Where the HERS rater verified index on
the building is 75 or fewer points for the finished building together with a
completed and HERS rater verified ENERGY STAR Thermal Enclosure Checklist. The
mandatory provisions of subsection 401.2 apply.
2.
Passive House Institute US (PHIUS)
Approved Software: Passive House Planning Package (PHPP). Where the
Specific Space Heat Demand as modeled in Passive House Planning Package (PHPP)
by a Certified Passive House Consultant is less than or equal to 20 KBtu/sq
ft/year. The mandatory provisions of subsection 401.2
apply.
405.7.1
Documentation. The following documentation is required for energy code
compliance under subsection 405.7:
1. For HERS
compliance, a compliance report which includes a proposed HERS index of 75 or
lower, a description of the building's energy features, and a statement that
the rating index is "based on plans" will be required for issuance of a
building permit. A copy of the final certificate indicating
that the HERS rater verified index is 75 or less for the finished building
together with a completed HERS rater verified ENERGY STAR Thermal Enclosure
Checklist is to be submitted to the building official before
the certificate of occupancy is issued.
2. For Passive House Planning Package (PHPP)
verified compliance, a compliance features, and a statement that the estimated
Specific Space Heat Demand is "based on plans" will be required for issuance of
a building permit. A copy of the final PHPP report indicating
the finished building achieves a Certified Passive House Consultant-verified
Specific Space Heat Demand of less than or equal to 20 KBtus/sq ft/year shall
be submitted to the building official before the certificate
of occupancy is issued.
N1101.2.1
Interior
Design Conditions. The interior design temperatures used for heating and
cooling load calculations shall be a maximum of 72°F (22°C) for heating
and minimum of 74°F (24°C) for cooling.
Table N1102.2.1 In the Climate Zone 5 row, replace
the value '.060' with '.057'.
N1102.2.2 Replace the second sentence as
follows: 'This reduction of insulation from the requirements of Section N1102.1
shall be limited to 500 square feet (46 m2) or 20% of the total insulated
ceiling area, whichever is less.'
Table N1102.2.1 To the criteria of the first row
of the table add 'Air-permeable insulation is inside of an air barrier' and to
the criteria of the fifth row of the table replace 'floor' with
'insulation'
N1102.5 Add subsection:
N1102.5
Maximum Fenestration U-factor
and SHGC. The area-weighted average maximum fenestration U-factor
permitted using trade-offs from Subsection N1102.1.3 or N1105 shall be 0.48.
N1103.8.3 Add an
exception as follows:
Exception. Pool covers deriving over 60% of the
energy for heating from site-recovered energy or solar energy
source.
M1201.1 Add a final
sentence as follows:
In this chapter where the design, installation, maintenance,
alteration and/or inspection of mechanical systems is controlled by one of the
specialized codes (see Chapter 1) the
requirements of the specialized codes govern and enforcement
shall be by a person other than the building official.
Chapter 12:
MECHANICAL ADMINISTRATION
M1201.1 Revise the section as follows:
M1201.1
Scope. The provisions of
Chapters 12 through 23 of 780 CMR 51.00 shall regulate the design,
installation, maintenance, alteration and inspection of mechanical systems that
are permanently installed and used to control environmental conditions within
buildings. These chapters shall also regulate those mechanical systems, system
components, equipment and appliances specifically addressed in this code.
For the provisions of Chapters 12 through 23 of 780 CMR 51.00
governed by the specialized codes (see780 CMR 1.00:
Scope and Administration (Unique to
Massachusetts)), see the applicable specialized
codes. Provisions related to work otherwise governed by 780 CMR 51.00 shall be
retained if not in conflict with other sections of 780 CMR 51.00. Enforcement
of work governed by the specialized codes shall be by those persons so
authorized.
Additional requirements for boilers and other pressure vessels
may be found in M.G.L. c. 146 and 522 CMR: Board of Boiler
Rules, as applicable.
Chapter 13:
GENERAL MECHANICAL SYSTEM
REQUIREMENTS
M1301.1 Add a final
sentence as follows:
In this chapter where the design, installation, maintenance,
alteration and/or inspection of mechanical systems is controlled by one of the
specialized codes (see Chapter 1) the
requirements of the specialized codes govern and enforcement
shall be by a person other than the building official.
M1303.2 Add subsection:
M1303.2
Solid Fuel-burning Appliance
Labeling. Solid fuel-burning appliances (
see Subsection
M1303.3 for Central Heating Appliances) shall bear a permanent and legible
factory-applied label supplied to the manufacturer and controlled by an
approved testing agency; such label shall contain the following information:
1. Manufacturer's name and
trademark;
2. Model and/or
identification number of the appliance;
3. Type(s) of fuel(s) approved;
4. Testing laboratory's name or trademark and
location;
5. Date tested;
6. Clearances to combustibles:
a. Above top
b. From front
c. From back
d. From sides
7. Floor protection*;
8. National test (listing) standard(s);
and
9. Label serial number.
*If floor protection information is not on the label, it will
be acceptable if contained with the User/Installation Manual.
M1303.3 Add subsection:
M1303.3
Solid Fuel-burning Central
Heating Appliance Labeling. Solid fuel-burning boilers or warm air
furnaces shall bear a permanent and legible factory-applied label supplied to
the manufacturer and controlled by an approved testing agency; such label shall
contain Subsection M1303.2 items 1. to 9. and the following information:
10. Type of appliance (boiler or warm air
furnace);
11. Boilers, pressure
vessels, and pressure relief devices must be stamped in accordance with M.G.L.
c. 146, §§ 24 and 34.
Chapter 14:
HEATING AND COOLING
EQUIPMENT
M1401.1 Add a final sentence
as follows:
In this chapter where the design, installation, maintenance,
alteration and/or inspection of mechanical systems is controlled by one of the
specialized codes (see Chapter 1) the
requirements of the specialized codes govern and enforcement
shall be by a person other than the building official.
M1401.6 Add section and associated
subsections as follows:
M1401.6
Used
Solid Fuel-burning Appliances. Used solid fuel-burning appliances that
predate the listing requirements set forth in 780 CMR 51.00 may be utilized but
the installation of such appliances shall otherwise conform to the requirements
of 780 CMR 51.00. as applicable, and such installations shall be inspected by
the building official (or fire official in such towns that utilize the fire
official for such inspection purposes).
M1401.6.1
Clearances to
Combustibles. In the absence of listed clearances and floor protection
requirements, used solid fuel-burning appliances shall be installed in
accordance with the clearances of 780 CMR 51.00.
M1401.6.2
Floor Protection
General. Floor protection listing requirements for a used appliance
shall be met. In the absence of listing requirements, solid fuel-burning
appliances shall have floor protection that is noncombustible material applied
to the combustible or noncombustible floor area underneath and extending in
front, to the sides and to the rear of a heat producing appliance, and have the
necessary thermal conductivity to satisfy the floor protection requirements of
the appliance. Various "hearth rugs," "mats," "tile board," "hearth board" and
similar products sold as floor protectors may be noncombustible but may not
satisfy thermal conductivity requirements of this section.
M1401.6.2.1
Floor Protection
Requirements. Floor protection requirements shall be:
1. four inches (102 mm) of millboard having a
thermal conductivity k = 0.84 (Btu) (inch)/(ft2)
(hour) (°F);
2. a
noncombustible floor protector of the same overall thermal conductivity in
(1.); or
3. approved by a
registered design professional.
Exception: If existing floor protection can be
demonstrated to have been adequate for a previous installation of a used solid
fuel-burning appliance, then such floor protection shall be allowed. If
calculations demonstrate that the existing floor protection has a thermal
conductivity lower than that set by this section, then the existing floor
protection may be maintained.
M1414.1 Revise the
section as follows:
M1414.1
General. Fireplace stoves shall be listed, labeled and installed
in accordance with the terms of the listing. Fireplace stoves shall be tested
in accordance with UL 737. Also see Chapter 10 of 780 CMR
51.00 for detailed guidance on solid fuel-burning
appliances.
Chapter
15:
EXHAUST SYSTEMS (no amendments)
M1501.1 Add a final sentence as follows:
In this chapter where the design, installation, maintenance,
alteration and/or inspection of mechanical systems is controlled by one of the
specialized codes (see Chapter 1) the
requirements of the specialized codes govern and enforcement
shall be by a person other than the building official.
M1507.1 Replace as follows:
M1507.1
General. Toilet rooms
and bathrooms shall be mechanically ventilated in accordance with the
requirements of Table M1507.3 and the ventilation equipment shall be installed
in accordance with this chapter and the governing specialized
codes.
Chapter
16:
DUCT SYSTEMS
M1601.1 Add a final sentence as follows:
In this chapter where the design, installation, maintenance,
alteration and/or inspection of mechanical systems is controlled by one of the
specialized codes (see Chapter 1) the
requirements of the specialized codes govern and enforcement
shall be by a person other than the building official.
M1601.3 Replace the section as
follows:
M1601.3
Duct Insulation
Materials. Duct insulation shall conform to the following requirements
and the requirements of Chapter 11 of 780 CMR 51.00.
M1601.4 Replace the section as follows:
M1601.4
Installation. Duct
installation shall comply with Subsections M1601.4.1 through M1601.4.7 and the
requirements of Chapter 11 of 780 CMR 51.00.
M1701.1 Replace as follows:
M1701.1
Scope.
Solid-fuel-burning appliances shall be provided with combustion air in
accordance with the appliance manufacturer's installation instructions.
Oil-fired appliances shall be provided with combustion air in accordance with
527 CMR 4.00: Oil
Burning Equipment. The methods of providing combustion air in this
chapter do not apply to fireplaces, fireplace stoves and direct-vent
appliances. The requirements for combustion and dilution air for gas-fired
appliances shall be in accordance with Chapter 24. In this chapter where the
design, installation, maintenance, alteration and/or inspection of mechanical
systems is controlled by one of the specialized codes
(see Chapter 1) the requirements of the specialized
codes govern and enforcement shall be by a person other than the
building official.
M1801.1 Replace the third sentence as
follows:
The requirements of this chapter shall not apply to gas-fired
and oil-fired appliances. For gas-fired appliances see the
Board of State Examiners of Plumbers and Gas Fitters regulations at 248 CMR.
For oil-fired appliances see527 CMR 4.00: Oil
Burning Equipment. For electrical requirements see527
CMR 12.00: Massachusetts Electrical Code
(Amendments). For fire prevention regulations 527 CMR governs, except
where 527 CMR is silent, in which case the International Fire
Code requirements, as applicable, apply. Solid fuel-burning appliances
shall satisfy the manufacturer's requirements, and in the absence of same, this
code shall apply.
M1801.11
Delete the Exception to subsection 1.
M1801.12 Add an Exception as follows:
Exception. Unless common connection is allowed by
248 CMR or 527 CMR. If allowed, the common flue shall be of such size to serve
all appliances connected if such appliances were operated simultaneously. Note
that 248 CMR and 527 CMR are enforced by gas inspectors, and the heads of fire
departments, respectively.
M1803.2 In the subsection title and the
paragraph delete the text "oil and"
M1900 Add section:
M1900
General. The requirement
of this chapter shall not apply to gas-fired and oil-fired appliances. For
gas-fired appliances see the Board of State Examiners of
Plumbers and Gas Fitters regulations at 248 CMR. For oil-fired appliances
see527 CMR 4.00: Oil
Burning Equipment. For electrical requirements see527
CMR 12.00: Massachusetts Electrical Code
(Amendments). For fire prevention regulations 527 CMR governs, except
where 527 CMR is silent, in which case the International Fire
Code requirements, as applicable, apply. Solid fuel-burning appliances
shall satisfy the manufacturer's requirements, and in the absence of same, this
code shall apply.
M2000
Add section:
M2000
General. The
requirement of this chapter shall not apply to gas-fired and oil-fired
appliances. For gas-fired appliances see the Board of State
Examiners of Plumbers and Gas Fitters regulations at 248 CMR. For oil-fired
appliances see527 CMR 4.00: Oil
Burning Equipment. For electrical requirements see527
CMR 12.00: Massachusetts Electrical Code
(Amendments). For fire prevention regulations 527 CMR governs, except
where 527 CMR is silent, in which case the International Fire
Code requirements, as applicable, apply. Solid fuel-burning appliances
shall satisfy the manufacturer's requirements, and in the absence of same, this
code shall apply. Additional requirements for boilers and other pressure
vessels may be found in M.G.L. c. 146 and the Board of Boiler Rules at 522 CMR,
as applicable.
M2100 Add
section:
M2100
General. The
requirement of this chapter shall not apply to gas-fired and oil-fired
appliances. For gas-fired appliances see the Board of State
Examiners of Plumbers and Gas Fitters regulations at 248 CMR. For oil-fired
appliances see527 CMR 4.00: Oil
Burning Equipment. For electrical requirements see527
CMR 12.00: Massachusetts Electrical Code
(Amendments). For fire prevention regulations 527 CMR governs, except
where 527 CMR is silent, in which case the International Fire
Code requirements, as applicable, apply. Solid fuel-burning appliances
shall satisfy the manufacturer's requirements, and in the absence of same, this
code shall apply. Additional requirements for boilers and other pressure
vessels may be found in M.G.L. c. 146 and the Board of Boiler Rules at 522 CMR,
as applicable.
M2101.3
Replace 'listed in Section P2902' with 'of the Department of Environmental
Protection and/or the local water purveyor, as applicable.'
M2201 through
M2204 Replace in
their entirety, as follows:
M2201
Special Piping and Storage Systems. Special laws and/or
regulations impact requirements for oil tanks, piping, fittings, connections,
installation, and oil pumps and valves. Refer to M.G.L. c. 148, § 13,
M.G.L. c. 148, § 37, the Board of Fire Prevention Regulations at 527 CMR,
the Board of Boiler Rules at 522 CMR and EPA regulations (as well as this code
for tank structural design).
M2301.1 Add three notes as follows:
Notes:
1.
Additional requirements for boilers and other pressure vessels may be found in
M.G.L. c. 146 and the Board of Boiler Rules at 522 CMR, as
applicable.
2. Where solar thermal
systems involve matters of potable water and/or wastewater see
the Board of State Examiners for Plumbers and Gas Fitters regulations at 248
CMR.
3. Photovoltaic systems shall
be designed and installed in accordance all governing loading conditions, fire
protection, energy conservation and weatherization requirements dictated by
this code and the electrical requirements of
527
CMR 12.00: Massachusetts Electrical Code
(Amendments) and those of the manufacturer.
2400 Add section:
2400
General. Retain the
sections listed in Table 2400. For all other requirements of this chapter
see the Board of State Examiners of Plumbers and Gas Fitters
regulations at 248 CMR.
TABLE 2400
G2404.6 (301.10) Wind resistance
|
G2427.5.6.1 (503.5.7.1) Solid fuel-burning
appliances
|
G2404.7 (301.11) Flood hazard
|
G2427.5.6.3 (503.5.7.3) Combination gas- and solid
fuel-burning appliances
|
G2404.8 (301.12) Seismic resistance
|
G2427.5.8 (503.5.9) Cleanouts
|
G2404.9 (301.14) Rodentproofing
|
G2427.5.9 (503.5.10) Space surrounding lining or
vent
|
G2405 Structural Safety
|
G2427.6.3.1 (503.6.4.1) Decorative shrouds
|
G2408.2 (305.3) Elevation of ignition source
|
G2427.7.5 (503.7.5) Roof penetrations
|
G2408.2.1 (305.3.1) Installation in residential
garages
|
G2427.10.13 (503.10.13) Fireplaces
|
G2408.3 (305.5) Private garages.
|
G2427.16 (503.16) (IFGC) Outside wall
penetrations
|
G2408.5 (305.8) Clearances to combustible
construction
|
G2430.2 (506.2) Support
|
G2415.1 (404.1) Prohibited locations
|
G2439.2 (614.2) Duct penetrations
|
G2415.5 (404.5) Protection against physical
damage
|
G2439.5 (614.6) Domestic clothes dryer exhaust
ducts
|
G2415.6 (404.6) Piping in solid floors
|
G2439.5.2 (614.6.2) Duct installation
|
G2418.2 (407.2) Design and installation
|
G2439.5.3 (614.6.3) Protection required
|
G2426.4 (502.4) Insulation shield
|
G2426.7 (502.7) Protection against physical
damage
|
G2427.5.3 (503.5.4) Chimney termination
|
G2445
(621) Replace this section
in its entirety as follows:
G2445.1
(621.1) General. Unvented gas-fired room heaters shall conform to
the requirements of
527 CMR 30.00:
Unvented Propane or Natural Gas-fired Space
Heaters.
G2452.1
(631.1) Add a last sentence as follows:
Additional requirements for boilers and other pressure vessels
may be found in M.G.L. c. 146 and the Board of Boiler Rules at 522 CMR, as
applicable.
P2501.1 Replace
all subsections of this chapter as follows:
P2501.1
Scope. For plumbing
requirements see248
CMR 10.00: Uniform State Plumbing
Code.
P2601.1
Replace as follows:
P2601.1
Scope. Retain the subsections listed in Table 2601.1. For all other
requirements of this chapter
see248
CMR 10.00:
Uniform State Plumbing
Code.
TABLE 2601.1
P2603.2 Drilling and notching
|
P2604.1 Trenching and bedding
|
P2603.2.1 Protection against physical damage
|
P2604.3 Backfilling
|
P2603.3 Breakage and corrosion
|
P2604.4 Protection of footings
|
P2603.5 Pipes through footings or foundation
walls
|
P2606.1 General
|
P2701.1 Replace all subsections of this
chapter as follows:
P2701.1
Scope. For plumbing fixture requirements see248
CMR 10.00: Uniform State Plumbing
Code.
P2801.1
Replace as follows:
P2801.1
Scope. Retain the subsections listed in Table 2801.1. For all
other requirements of this chapter
see248
CMR 10.00:
Uniform State Plumbing
Code.
TABLE 2801.1
P2801.5 Required pan (if not in 248 CMR)
|
P2801.7 Water heater seismic bracing.
|
P2801.6 Water heaters installed in garages.
|
P2901.1 Replace all subsections of this
chapter as follows:
P2901.1
Scope. For plumbing requirements for water supply and distribution
see248
CMR 10.00: Uniform State Plumbing
Code.
310 CMR
22.00: Drinking Water and/or the
local water purveyor, as applicable, govern backflow protection requirements.
Fire Sprinkler requirements are found in Chapter 3.
P3001.1 Replace all subsections of this
chapter as follows:
P3001.1
Scope. For municipal sewage disposal see248
CMR 10.00: Uniform State Plumbing
Code and for private sewage disposal see310 CMR
15.00: The State Environmental Code, Title 5: Standard Requirements for
the Siting, Construction, Inspection, Upgrade and Expansion of On-site Sewage
Treatment and Disposal Systems and for the Transport and Disposal of
Septage.
P3101.1
Replace all subsections of this chapter as follows:
P3101.1
General. For vent
requirements see the Board of State Examiners of Plumbers and
Gas Fitters regulations at 248 CMR.
P3201.1 Replace all subsections of this
chapter as follows:
P3201.1
General. For trap requirements see248
CMR 10.00: Uniform State Plumbing
Code.
P3301.1
Replace all subsections of this chapter as follows:
P3301.1
Scope. For storm
drainage requirements
see the applicable requirements of:
1.248
CMR 10.00: Uniform State Plumbing
Code,
2. Division of Water
Pollution Control regulations at 314 CMR, and
3. Local municipal requirements.
E3401.1 Replace all
subsections of this chapter as follows:
E3401.1
Applicability. Retain
the subsections listed in Table 3401.1. For all other requirements of this
chapter
see527
CMR 12.00:
Massachusetts Electrical Code
(Amenrments).
TABLE 3401.1
E3402.1 Drilling and notching
|
3402.3 Penetrations of firestops and
draftstops.
|
E3402.2 Penetrations of fire-resistance-rated
assemblies
|
E3501.1 Replace all subsections of this
chapter as follows:
E3501.1
Scope. For electrical definitions see527
CMR 12.00: Massachusetts Electrical Code
(Amendments).
E3601.1 Replace all subsections of this
chapter as follows:
E3601.1
Scope. For electrical services see527
CMR 12.00: Massachusetts Electrical Code
(Amendments).
E3701.1 Replace all subsections of this
chapter as follows:
E3701.1
Scope. For branch circuit and feeder requirements
see527
CMR 12.00: Massachusetts Electrical Code
(Amendments).
E3801.1 Replace all subsections of this
chapter as follows:
E3801.1
Scope. Retain the table or subsections listed in Table 3801.1. For
all other requirements of this chapter
see527
CMR 12.00:
Massachusetts Electrical Code
(Amendments).
TABLE 3801.1
E3802.2.1 Across structural members
|
Table E3802.1: (Subjects which pertain to framing or
protection).
|
E3802.2.2 Cable installed through or parallel to
framing members
|
E3901.1 Replace all subsections of this
chapter as follows:
E3901.1
General. For power and lighting distribution requirements
see527
CMR 12.00: Massachusetts Electrical Code
(Amendments).
4000 Add section:
4000
Scope. For devices and
luminaires requirements see527
CMR 12.00: Massachusetts Electrical Code
(Amendments).
E4101.1 Replace all subsections of this
chapter as follows:
E4101.1
General. For appliance installation requirements
see527
CMR 12.00: Massachusetts Electrical Code
(Amendments).
E4201.1 At the end of this subsection add two
sentences as follows:
For electrical requirements see527
CMR 12.00: Massachusetts Electrical Code
(Amendments). For pool barrier and other pool safety requirements,
see Appendix G.
E4301.1 Replace all subsections of this
chapter as follows:
E4301.1
Scope. For Class 2 remote-control, signaling and power-limited
circuit requirements see527
CMR 12.00: Massachusetts Electrical Code
(Amendments).
CHAPTER 44 Add standards as follows:
NFPA 13R-07 Standard for the Installation of Sprinkler Systems
in Residential Occupancies up to and Including Four Stories in Height.
NFPA 720-09 Standard for the Installation of Carbon Monoxide
(CO) Detection and Warning Equipment
APPENDIX A - SIZING AND CAPACITIES OF GAS
PIPING
A.0 Add section:
A.0
General. Delete all sections
of this Appendix and for requirements see the Board of State
Examiners of Plumbers and Gas Fitters regulations at 248
CMR.
APPENDIX B - SIZING OF VENTING SYSTEMS SERVING APPLIANCES
EQUIPPED WITHDRAFT HOODS, CATEGORY 1 APPLIANCES, AND APPLIANCES LISTED FOR USE
WITH TYPE B VENTS
B.0 Add
section:
B.0
General. Delete all
sections of this Appendix and for requirements see the Board
of State Examiners of Plumbers and Gas Fitters regulations at 248
CMR.
APPENDIX C - EXIT TERMINALS OF MECHANICAL DRAFT AND
DIRECT-VENT VENTING SYSTEMS
C.0
Add section:
C.0
General. Exit
terminals of gas-fired mechanical draft and direct-vent venting systems shall
conform to the applicable requirements of the Board of State Examiners of
Plumbers and Gas Fitters regulations at 248 CMR.
Exit terminals of oil-fired mechanical draft and direct-vent
venting systems shall conform to the applicable requirements of
527 CMR 4.00: Oil
Burning Equipment or, in the absence of such guidance, shall conform
to the criteria of Figure C-1, or the equipment manufacturer's requirements,
whichever are more stringent.
Exit terminals of solid fuel-burning mechanical draft and
direct-vent venting systems shall conform to the applicable requirements of
Figure C-1, or the equipment manufacturer's requirements, whichever are more
stringent.
APPENDIX D - RECOMMENDED PROCEDURE FOR SAFETY INSPECTION
OF AN EXISTING APPLIANCE INSTALLATION: Reserved.
APPENDIX E - MANUFACTURED HOUSING USED AS
DWELLINGS
AE101.1 Add a note as
follows:
Note. Construction, installation, addition, repair
or maintenance of building systems that fall under that authority of the
specialized codes shall be overridden by and shall conform to
applicable specialized code(s) requirements.
AE102.2 Replace subsections 1., 2., and 3. as
follows:
1. Be designed and constructed in
conformance with this code and the applicable s
pecialized
codes.
AE301 to AE304 Replace as
follows:
AE301.1
Permits and Fees. For permit requirements
see Chapter 1. Refer to local municipality for
permit fees.
AE305
Replace as follows:
AE305.1
General. For inspection requirements see Chapter
1.
AE507.1 Replace as
follows:
AE507.1
General.
Alterations made to a manufactured home subsequent to its initial installation
shall conform to the occupancy, fire-safety and energy conservation
requirements of this code.
Appendix F: PASSIVE RADON GAS CONTROLS (Adopted as
revised)
AF101.1 Revise the section as
follows:
AF101.1
General. This
appendix contains minimum requirements for new construction in the high radon
potential counties as listed in Table AF101(1) regardless of the radon levels
at the site. These requirements are intended to provide a passive means of
resisting radon gas entry and prepare the dwelling for post-construction radon
mitigation, if necessary.
See Figure AF102. Active
construction techniques, rather than passive techniques, shall be permitted to
be used where approved.
Alternatively, the passive system requirements of ANSI/AARST
Standard Designation #CCAH: Reducing Radon in New Construction of One
& Two Family Dwellings and Townhouses, 2013 may be used for new
construction in Zone 1, or approved equal system.
Irrespective of which approach is used, no testing is required
as follows:
1. for the radon levels at
the site prior to construction;
2.
for the radon control system when completed; or
3. in the building after completion of the
project.
Therefore, such testing shall not be a condition of issuing a
certificate of occupancy.
AF102.1 Revise the definition of
"GAS-PERMEABLE LAYER" as follows:
GAS-PERMEABLE LAYER. A gas-permeable layer shall
consist of one of the following:
1. A
uniform layer of clean aggregate that is not less than four inches (102 mm)
thick. The aggregate shall consist of material that will pass through a two
inch (51 mm) sieve and be retained by a 1/4-inch (6.4-mm) sieve.
2. A uniform layer of sand (native or fill)
that is not less than four inches (102 mm) thick and that is overlain by a soil
gas collection mat or soil gas matting installed in accordance with the
manufacturer's instructions. The soil gas mat or matting shall be designed for
this purpose and condition, and have the capacity to freely transport soil
gases to the collection point from the most remote area.
AF103.2.2 Revise the subsection as
follows:
AF103.2.2
Sumps. Sumps
open to soil or serving as the termination point for subslab drain tile loops
shall be covered with a gasketed or sealed lid. Sumps used as the suction point
in a sub slab depressurization system shall have a lid designed to accommodate
the vent pipe. Sumps used as a floor drain shall have a lid equipped with a
trapped inlet. Drainage systems that lead outside the foundation walls shall be
isolated or trapped so as not to short-circuit the depressurization
system.
AF103.3.1 Revise
the subsection as follows:
AF103.3.1
Soil-gas-retarder. The soil in basements and enclosed crawl spaces
shall be covered with a soil-gas-retarder. The soil-gas-retarder shall be
lapped not less than 12 inches (305 mm) at joints and shall extend to
foundation walls enclosing the basement or crawl space. The soil gas-retarder
shall fit closely around any pipe, wire or other penetrations of the material.
Punctures or tears in the material shall be sealed or covered with additional
sheeting. The membrane shall extend upward six inches and shall be sealed to
the perimeter footing or wall with an ASTM C290 class 25 or higher sealant or
equal.
AF103.3.2 Revise
the subsection as follows:
AF103.3.2
"T" Fitting and Vent Pipe. A "T" fitting shall be inserted beneath
the soil-gas-retarder and be connected to a three-inch minimum vertical vent
pipe. The vent pipe shall extend through the conditioned space of the dwelling
and terminate not less than 12 inches (305 mm) above the roof in a location not
less than ten feet (3,048 mm) away from any window or other opening into the
conditioned spaces of the building that is less than two feet (610 mm) below
the exhaust point. The horizontal legs of the "T" fitting shall connect to two
five-foot long pieces of four-inch diameter perforated pipe laid horizontally
in a 50 in2 bed of gravel, filled with the same
gravel as used in the gas-permeable layer.
AF103.4.2 Revise the subsection as follows:
AF103.4.2
Soil-gas-retarder. A
soil-gas-retarder shall be placed on top of the gas-permeable layer prior to
casting the slab or placing the floor assembly. The soil-gas retarder shall
cover the entire floor area with separate sections lapped not less than 12
inches (305 mm) and shall extend upward six inches and be sealed to the wall
with an ASTM C290 class 25 or higher sealant or equal. The soil-gas-retarder
shall fit closely around any pipe, wire, or other penetrations of the material.
Punctures or tears in the material shall be sealed or covered. Under-slab
insulation, if used, shall be placed on top of the
sheeting.
AF103.4.3
Revise the subsection as follows:
AF103.4.3
"T" Fitting and Vent Pipe. Before a slab is cast or other floor
system is installed, a "T" fitting shall be inserted below the slab or other
floor system and the soil-gas-retarder. The "T" fitting shall be connected to a
three-inch minimum vertical vent pipe. The vent pipe shall extend through the
conditioned space of the dwelling and terminate not less than 12 inches (305
mm) above the roof in a location not less than ten feet (3,048 mm) away from
any window or other opening into the conditioned spaces of the building that is
less than two feet (610 mm) below the exhaust point. The horizontal legs of the
"T" fitting shall connect to two five-foot long pieces of four-inch diameter
perforated pipe laid horizontally in a 50 in2 bed of
gravel, filled with the same gravel as used in the gas-permeable
layer.
Appendix G: PIPING STANDARDS FOR VARIOUS APPLICATIONS
(Reserved)
Appendix H: PATIO COVERS (Adopted in full)
Appendix I: PRIVATE SEWAGE DISPOSAL (Adopted as
modified herein)
AI101.1 Revise the
section as follows:
AI101.1
Scope. Private sewage disposal systems shall conform to the requirements
of
310 CMR 15.000: The
State Environmental Code, Title 5: Standard Requirements for
the Siting, Construction, Inspection, Upgrade and Expansion of On-site Sewage
Treatment and Disposal Systems and for the Transport and Disposal of
Septage, and any additional legal restrictions imposed by the
municipal health department.
Appendix J: EXISTING BUILDINGS AND STRUCTURES
(Adopted as modified herein)
AJ101.1 Revise the section as follows:
AJ101.1
General. The purpose of
Appendix J is to encourage the continued use or reuse of
legally existing buildings and structures. The provisions of
Appendix J
are intended to permit work in existing buildings that is consistent
with the purpose of 780 CMR 51.00. Compliance with these provisions shall be
deemed to meet the requirements of 780 CMR 51.00.
Features of existing construction which do not meet the
requirements of 780 CMR 51.00 for new construction shall be presumed to have
met the regulations, codes or laws in effect at the time of construction or
alteration and, if so, shall be deemed to be existing nonconforming. Unless
stated otherwise, nothing in Appendix J shall require the
upgrading or replacement of any existing nonconforming feature or component of
an existing building, provided the feature, component or system is in
serviceable condition. Components or features of an existing building which, in
the opinion of the building official, are dangerous, unsafe, damaged,
significantly deteriorated or which otherwise present a threat to occupants or
to public safety shall be remediated in accordance with 780 CMR 51.00.
Any new building system or portion thereof shall conform to 780
CMR 51.00 for new construction to the fullest extent practicable. However,
individual components of an existing building system may be repaired or
replaced without requiring that system to comply fully with 780 CMR 51.00
unless specifically required by Appendix J.
For compliance of work governed by other codes, including the
specialized codes, see section R101.4.
AJ101.1.1
Buildings Which
Qualify. A building erected prior to the date of adoption of the
appropriate code, or one for which a legal building
permit has
been issued.
Note. Existing townhouse buildings regulated by
this code shall also conform to the seismic requirements of this
code.
AJ102.1 Replace the phrase "mechanical or
plumbing system" with "system controlled by this code"
AJ102.3 Replace as follows:
AJ102.3
Smoke, Heat, Carbon Monoxide
Detection and Alarm Systems. When one or more sleeping rooms are added
or created in existing dwellings, the entire existing dwelling shall be
provided with smoke detectors, heat detector and carbon monoxide detectors
designed, located and installed in accordance with the provisions for new
construction, as applicable. If a garage is created under an existing dwelling
or attached to an existing dwelling, a heat detector, conforming to the
requirements of the code for new construction shall be installed in the garage;
such requirement is not applicable for detached garages (
see
Chapter 3).
If the dwelling undergoes complete reconstruction such that all
walls and ceilings are open to framing, then the entire existing building shall
be provided with smoke detectors, heat detector and carbon monoxide detectors
designed, located and installed in accordance with the provisions for new
construction.
In an existing two-family dwelling, if one or more sleeping
rooms are added or created in only one of the two dwelling units, the dwelling
unit acquiring new sleeping rooms shall be provided with smoke detectors, heat
detector and carbon monoxide detectors, as applicable, designed, located and
installed in accordance with the provisions for new construction.
In an existing two-family dwelling, if, during a
repair/reconstruction event, one or more sleeping rooms are added or created in
both of the two dwelling units, the entire building shall be provided with
smoke detectors, heat detector and carbon monoxide detectors, as applicable,
designed, located and installed in accordance with the provisions for new
construction for two-family dwellings.
Note 1. It is the intention of this code to
require that all required smoke alarms and required CO alarms be interconnected
by hard-wire methods or acceptable wireless methods per the interconnection
requirements of NFPA 72; additionally, required heat detectors are either to
activate sounders or be compatible with the smoke alarm system so that heat
activation of the heat detector operates a sounder or the smoke alarms of all
interconnected smoke alarms sound if heat is detected by the interconnected
heat detector. Where combination smoke/CO alarms are utilized, such are to be
interconnected and fire alarm signals have precedence over CO alarm in
accordance with the requirements of NFPA 720.
Note 2. CO detector requirements for existing
R-uses are also governed by
527 CMR 31.00: Carbon
Monoxide Alarms and the Board of State Examiners of Plumbers and Gas
Fitters at 248 CMR.
AJ102.7.1 Add subsection:
AJ102.7.1
Documentation of Compliance
Alternatives. The building official shall ensure that
the BBRS is provided with information regarding the compliance alternatives
accepted by the building official.
AJ102.10 Add subsection:
AJ102.10
Unlined Chimneys. Where
new HVAC appliances are connected to an unlined chimney, the chimney lining
requirements of the Board of State Examiners of Plumbers and Gas Fitters
regulations at 248 CMR or the Board of Fire Prevention regulations at 527 CMR,
as applicable, and those of the appliance manufacturer shall be satisfied. If
the appliance is a solid fuel-burning appliance, the chimney shall be relined
to satisfy requirements both of the code for new construction and those of the
manufacturer, as applicable.
AJ102.11 Add subsection:
AJ102.11
Latent Conditions. When
latent conditions are observed and which are determined by the licensed
construction supervisor, the owner or the
building official to
be dangerous or unsafe, or when a component or system is determined to be
unserviceable, said conditions shall be corrected in accordance with applicable
provisions of this code. A building
permit shall be obtained
or the building
permit shall be amended in accordance with the
provisions of Section R105 in order to reflect the necessary required work and
the approval shall be obtained from the
building official
prior to commencement of the corrections.
Exception. If the public safety so warrants, the
building permittable corrective actions are permitted to be made prior to
amending the building permit application, providing that the
building official is notified in writing within 24 hours of
actions taken pursuant to this exception. This exception shall not be construed
as to authorize constructive approval nor set aside the requirements to amend
the permit application, nor shall the authority of the
building official to enforce this code be abridged. Such
corrective actions shall be documented by the construction supervisor or the
owner and submitted to the building official within 48 hours
of the completion of the action under this exception. Such corrective work
shall not be concealed until the building official has
inspected and approved the work.
AJ102.12 Add subsection:
AJ102.12
Existing non Conforming Means
of Egress. The following conditions, when observed by the
building official, and believed shall be cited, in writing as
a violation. Said citation shall order the abatement of the non conformance and
shall include such a time element as the
building official
deems necessary for the protection of the occupants thereof, or as otherwise
provided for by statute.
1. Less than the
number of means of egress serving every space and/or story,
required by this code.
2. Any
required means of egress component which is not of sufficient
width to comply with the code for new construction, or is not so arranged as to
provide safe and adequate means of egress.
AJ102.13 Add subsection:
AJ102.13
Hazardous Means of
Egress. In any existing building or structure not
provided with exit facilities as herein prescribed for new buildings and in
which the exits are deemed hazardous or dangerous to life and limb, the
building official shall declare such building dangerous and
unsafe in accordance with the provisions of Section R115.1.
AJ102.14 Add subsection:
AJ102.14
Roofing and Reroofing.
See Chapter 9 generally and Section R907.
AJ102.15 Add subsection:
AJ102.15
Additions. New
construction additions shall comply with all requirements of the code for new
construction.
AJ102.16
Add subsection:
AJ102.16
Accessibility
for Persons with Disabilities. Accessibility requirements shall be in
accordance with 521 CMR.
AJ301.1. Replace "designee shall" with "legal
designee may"
AJ301.1.2
Delete.
AJ301.2
Delete.
AJ301.4 Delete.
AJ401.2.1 Add subsection:
AJ401.2.1
Emergency Egress
Windows. For one- and two-family dwellings and townhouses of no more
than three stories in height, all emergency escape windows from sleeping rooms
shall have a net clear opening of 3.3 square feet (0.307
m2). The minimum net clear opening shall be 20
inches by 24 inches (508 mm by 610 mm) in either direction except that windows
in sleeping rooms of existing dwellings which do not conform to these
requirements may be replaced without conforming to these dimensional
requirements, provided that the windows do not significantly reduce the
existing opening size.
Exception. Replacement windows utilized as
emergency egress windows, other than double-hung windows, shall generally
conform to the requirements of this section without conforming to the cited
dimensional requirements, provided that such replacement windows do not
significantly reduce the existing opening size.
AJ401.4 Replace as follows:
AJ401.4
Structural. Unreinforced
masonry townhouse buildings shall have parapet bracing and wall anchors
installed at the roofline whenever a reroofing permit is
issued if required by 780 CMR 34.00: Existing Structures. Such
parapet bracing and wall anchors shall be of an approved
design. Where renovations may decrease the structural performance of the
existing building, such proposed activities shall be evaluated by a
registered design professional for adequacy, prior to such
actual structural renovation.
AJ501.4 Revise the subsection as follows:
AJ501.4
Structural. The minimum
design loads for the structure shall be the loads applicable at the time the
building was constructed, provided that a dangerous condition is not created.
Structural elements that are uncovered during the course of the alteration and
that are found to be unsound or dangerous shall be made to comply with the
applicable requirements of 780 CMR 51.00. Where alterations may decrease the
structural performance of the existing building, such proposed activities shall
be evaluated by a registered design professional for adequacy, prior to such
actual structural alterations.
AJ501.5 Revise the subsection as follows:
AJ501.5
Electrical Equipment and
Wiring. See527
CMR 12.00: Massachusetts Electrical Code
(Amendments).
AJ601.5 Add a subsection as follows:
AJ601.5
Structural. Where
reconstruction may decrease the structural performance of the existing
building, such proposed activities shall be evaluated by a registered design
professional for adequacy, prior to such actual structural
reconstruction.
AJ701 Add
a section as follows:
AJ701
HISTORIC
BUILDINGSAJ701.1
General. For historic building requirements,
see780 CMR
34.00:
Existing Building Code.
Appendix K: SOUND TRANSMISSION (Adopted in
full)
Appendix L: PERMIT FEES (see801 CMR
4.00: Rates, as applicable)
(Reserved)
Appendix M: HOME DAY CARE - R-3 OCCUPANCY
(Reserved)
Appendix N: VENTING METHODS (Reserved)
Appendix O: AUTOMATIC VEHICULAR GATES (Adopted in
full)
Appendix P: SIZING OF WATER PIPING SYSTEM
(Reserved)
Appendix Q (Reserved)
Appendix R: LIGHT STRAW-CLAY CONSTRUCTION
(Reserved)
Appendix S: STRAWABLE CONSTRUCTION
(Reserved)
Appendix T: RECOMMENDED PROCEDURE FOR WORST-CASE TESTING
OF ATMOSPHERIC VENTING SYSTEMS UNDER N1102.4 OR N1105 CONDITIONS
<= 5 ACH50 (Reserved)
Appendix U: SOLAR-READY PROVISIONS - DETACHED ONE-AND
TWO-FAMILY DWELLINGS, MULTIPLE SINGLE-FAMILY DWELLINGS (TOWNHOUSES)
(Adopted as modified herein)
Delete Appendix U
Delete IECC Appendix RA and replace with Appendix
RA as follows:
SECTION RA101
SCOPE
AU101.1
General. These
provisions shall be applicable for new construction, except additions.
SECTION RA102 GENERAL DEFINITIONS
Solar-ready Zone. A section or sections of the
roof or building overhang designated and reserved for the future installation
of a solar photovoltaic or solar thermal system.
SECTION RA103 SOLAR-READY ZONE
RA103.1
General. New detached
one- and two-family dwellings, and multiple single-family dwellings
(townhouses) with not less than 600 ft2 (55.74
m2) of roof area oriented between 110° and
270° of true north shall comply with sections RA103.2 through RA103.8.
Exceptions:
1. New residential buildings with a
permanently installed on-site renewable energy system.
2. A building with a solar-ready zone that is
shaded for more than 70% of daylight hours annually.
3. Buildings and structures as designed and
shown in construction documents that do not meet the conditions for a
solar-ready zone area.x
RA103.2
Construction Document
Requirements for Solar-ready Zone. Construction documents shall indicate
the solar-ready zone where applicable.
RA103.3
Solar-ready Zone Area.
The total solar-ready zone area shall consist of an area not less than 300
ft2 (27.87 m2) exclusive
of mandatory access or set back areas as required by 527 CMR: Board of
Fire Prevention Regulations. New multiple single-family dwellings
(townhouses) three stories or less in height above grade plane and with a total
floor area less than or equal to 2,000 ft2 (185.8
m2) per dwelling shall have a solar-ready zone area
of not less than 150 ft2 (13.94
m2). The solar-ready zone shall be composed of areas
not less than five feet (1,524 mm) in width and not less than 80
ft2 (7.44 m2) exclusive
of access or set back areas as required by 527 CMR.
RA103.4
Obstructions.
Solar-ready zones shall consist of an area free from obstructions including,
but not limited to, vents, chimneys, and roof-mounted equipment.
Note: Nothing in RA103.4 shall require any
construction documents to be redesigned or reconfigured so as to create a
solar-ready zone area.
RA103.5
Roof Load Documentation.
The structural design loads for roof dead load and roof live load shall be
clearly indicated on the construction documents.
RA103.6
Interconnection Pathway.
Construction documents shall indicate pathways for routing of conduit or
plumbing from the solar-ready zone to the electrical service panel or service
hot water system.
RA103.7
Reserved.
RA103.8
Construction Documentation Certificate. A permanent certificate,
indicating the solar-ready zone and other requirements of this section, shall
be posted near the electrical distribution panel, water heater or other
conspicuous location by the builder or registered design
professional.
Appendix AA STRETCH ENERGY CODE
AA101
Purpose and Adoption. The
purpose of the stretch energy code is to provide a more energy efficient code
alternative for new buildings. The stretch energy code may be adopted or
rescinded by any municipality in the commonwealth in the manner prescribed by
law.
AA102
Applicability. Municipalities that have adopted the stretch energy
code shall use the energy efficiency requirements of this appendix as provided
in AA103 and AA104. These requirements replace all previous stretch energy code
requirements.
AA103
New
Buildings.
AA103.1
R-use
Buildings. In all R-use buildings, of four stories or less above grade
plane with one or more dwelling units, each dwelling unit shall comply with
IECC 2018 section R406 of 780 CMR 51.00 and all mandatory requirements of 780
CMR 13.00: Energy Efficiency and 51.00, as
applicable.
AA103.2
Large Area
and High Energy Use Buildings. All buildings over 100,000
ft2, and new supermarkets, laboratories and
conditioned warehouses over 40,000 ft2 shall comply
with 780 CMR 13.00: Energy Efficiency and shall demonstrate
energy use per ft2 at least 10% below the energy
requirements of ANSI/ASHRAE/IESNA 90.1 Appendix G Performance
Rating Method on either a site or source energy basis. The additional
efficiency package options selected in accordance with C406.1 shall be included
in calculating the baseline building performance value.
Exception: Exclusively R-use buildings complying
with AA103.1 dwelling unit requirements.
AA103.3
Other New Buildings. New
buildings not covered in AA103.1 and AA103.2 shall comply with 780 CMR 13.00:
Energy Efficiency or Chapter 11 of 780 CMR 51.00 as applicable
based on the use and occupancy of the building.
AA104
Existing Buildings. For
alterations, renovations, additions or repairs of existing buildings in these
municipalities, the energy efficiency requirements of 780 CMR 13.00:
Energy Efficiency or Chapter 11 of 780 CMR 51.00 shall be used
as applicable based on the use and occupancy of the
building.