Code of Massachusetts Regulations
780 CMR - STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
Chapter 5 - General Building Heights and Areas
Section 508 - MIXED USE AND OCCUPANCY
Subsection 508.2 - Accessory occupancies
Current through Register 1531, September 27, 2024
Accessory occupancies are those occupancies that are ancillary to the main occupancy of the building or portion thereof. Accessory occupancies shall comply with the provisions of Sections 508.2.1 through 508.2.5.3.
508.2.1 Area limitations. Aggregate accessory occupancies shall not occupy more than 10 percent of the building area of the story in which they are located and shall not exceed the tabular values in Table 503, without building area increases in accordance with Section 506 for such accessory occupancies.
508.2.2 Occupancy classification. Accessory occupancies shall be individually classified in accordance with Section 302.1. The requirements of this code shall apply to each portion of the building based on the occupancy classification of that space.
508.2.3 Allowable building area and height. The allowable building area and height of the building shall be based on the allowable building area and height for the main occupancy in accordance with Section 503.1. The height of each accessory occupancy shall not exceed the tabular values in Table 503, without increases in accordance with Section 504 for such accessory occupancies. The building area of the accessory occupancies shall be in accordance with Section 508.2.1.
508.2.4 Separation of occupancies. No separation is required between accessory occupancies and the main occupancy.
Exceptions:
508.2.5 Separation of incidental accessory occupancies. The incidental accessory occupancies listed in Table 508.2.5 shall be separated from the remainder of the building or equipped with an automatic fire-extinguishing system, or both, in accordance with Table 508.2.5.
Exception: Incidental accessory occupancies within and serving a dwelling unit are not required to comply with this section.
TABLE 508.2.5 INCIDENTAL ACCESSORY OCCUPANCIES
ROOM OR AREA | SEPARATION AND/OR PROTECTION |
Furnace room where any piece of equipment is over
400,000 Btu per hour input |
1 hour or provide automatic fire-extinguishing system |
Rooms with boilers where the largest piece of
equipment is over 15 psi and 10 horsepower |
1 hour or provide automatic fire-extinguishing system |
Refrigerant machinery room | 1 hour or provide automatic sprinkler system |
Hydrogen cutoff rooms, not classified as Group H | 1 hour in Group B, F, M, S and U occupancies; 2 hours
in Group A, E, I and R occupancies. |
Incinerator rooms | 2 hours and automatic sprinkler system |
Paint shops, not classified as Group H, located in occupancies other than Group F | 2 hours; or 1 hour and provide automatic fire-extinguishing system |
Laboratories and vocational shops, not classified as
Group H, located in a Group E or I-2 occupancy |
1 hour or provide automatic fire-extinguishing system |
Laundry rooms over 100 square feet | 1 hour or provide automatic fire-extinguishing system |
Group I-3 cells equipped with padded surfaces | 1 hour |
Group I-2 waste and linen collection rooms | 1 hour |
Waste and linen collection rooms over 100 square feet | 1 hour or provide automatic fire-extinguishing system |
Stationary storage battery systems having a liquid
electrolyte capacity of more than 50 gallons, or a lithium-ion capacity of 1,000 pounds used for facility standby power, emergency power or uninterrupted power supplies |
1 hour in Group B, F, M, S and U occupancies; 2 hours
in Group A, E, I and R occupancies. |
Rooms containing fire pumps in nonhigh-rise buildings | 2 hours; or 1 hour and provide automatic sprinkler system throughout the building |
Rooms containing fire pumps in high-rise buildings | 2 hours |
For SI: 1 square foot = 0.0929 m2, 1 pound per square inch (psi) = 6.9 kPa, 1 British thermal unit (Btu) per hour = 0.293 watts, 1 horsepower = 746 watts, 1 gallon = 3.785 L. |