Section 503 - GENERAL BUILDING HEIGHT AND AREA LIMITATIONS


Current through Register 1531, September 27, 2024

TABLE 503 ALLOWABLE BUILDING HEIGHTS AND AREASa

Building height limitations shown in feet above grade plane. Story limitations shown as stories above grade plane. Building area limitations shown in square feet, as determined by the definition of "Area, building," per story

GROUP TYPE OF CONSTRUCTION
TYPE I TYPE II TYPE III TYPE IV TYPE V
A B A B A B HT A B
HEIGHT (feet) UL 160 65 55 65 55 65 50 40
STORIES(S) AREA (A)
A-1 S A UL UL 5 UL 3 15,500 2 8,500 3 14,000 2 8,500 3 15,000 2 11,500 1 5,500
A-2 S A UL UL 11 UL 3 15,500 2 9,500 3 14,000 2 9,500 3 15,000 2 11,500 1 6,000
A-3 S A UL UL 11 UL 3 15,500 2 9,500 3 14,000 2 9,500 3 15,000 2 11,500 1 6,000
A-4 S A UL UL 11 UL 3 15,500 2 9,500 3 14,000 2 9,500 3 15,000 2 11,500 1 6,000
A-5 S A UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL
B S A UL UL 11 UL 5 37,500 3 23,000 5 28,500 3 19,000 5 36,000 3 18,000 2 9,000
E S A UL UL 5 UL 3 26,500 2 14,500 3 23,500 2 14,500 3 25,500 1 18,500 1 9,500
F-1 S A UL UL 11 UL 4 25,000 2 15,500 3 19,000 2 12,000 4 33,500 2 14,000 1 8,500
F-2 S A UL UL 11 UL 5 37,500 3 23,000 4 28,500 3 18,000 5 50,500 3 21,000 2 13,000
H-1 S A 1 21,000 1 16,500 1 11,000 1 7,000 1 9,500 1 7,000 1 10,500 1 7,500 NP NP
H-2d S A UL 21,000 3 16,500 2 11,000 1 7,000 2 9,500 1 7,000 2 10,500 1 7,500 1 3,000
H-3d S A UL UL 6 60,000 4 26,500 2 14,000 4 17,500 2 13,000 4 25,500 2 10,000 1 5,000
H-4 S A UL UL 7 UL 5 37,500 3 17,500 5 28,500 3 17,500 5 36,000 3 18,000 2 6,500
H-5 S A 4 UL 4 UL 3 37,500 3 23,000 3 28,500 3 19,000 3 36,000 3 18,000 2 9,000
I-1 S A UL UL 9 55,000 4 19,000 3 10,000 4 16,500 3 10,000 4 18,000 3 10,500 2 4,500
I-2 S A UL UL 4 UL 2 15,000 1 11,000 1 12,000 NP NP 1 12,000 1 9,500 NP NP
I-3 S A UL UL 4 UL 2 15,000 1 10,000 2 10,500 1 7,500 2 12,000 2 7,500 1 5,000
I-4 S A UL UL 5 60,500 3 26,500 2 13,000 3 23,500 2 13,000 3 25,500 1 18,500 1 9,000
M S A UL UL 11 UL 4 21,500 2 12,500 4 18,500 2 12,500 4 20,500 3 14,000 1 9,000
R-1 S A UL UL 11 UL 4 24,000 4 16,000 4 24,000 4 16,000 4 20,500 3 12,000 2 7,000
R-2 S A UL UL 11 UL 4 24,000 4 16,000 4 24,000 4 16,000 4 20,500 3 12,000 2 7,000
R-3 S A UL UL 11 UL 4 UL 4 UL 4 UL 4 UL 4 UL 3 UL 3 UL
R-4 S A UL UL 11 UL 4 24,000 4 16,000 4 24,000 4 16,000 4 20,500 3 12,000 2 7,000
S-1 S A UL UL 11 48,000 4 26,000 2 17,500 3 26,000 2 17,500 4 25,500 3 14,000 1 9,000
S-2b, c S A UL UL 11 79,000 5 39,000 3 26,000 4 39,000 3 26,000 5 38,500 4 21,000 2 13,500
Uc S A UL UL 5 35,500 4 19,000 2 8,500 3 14,000 2 8,500 4 18,000 2 9,000 1 5,500

For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2.
A = building area per story, S = stories above grade plane, UL = Unlimited, NP = Not permitted.
a. See the following sections for general exceptions to Table 503:
1. Section 504.2, Allowable building height and story increase due to automatic sprinkler system installation.
2. Section 506.2, Allowable building area increase due to street frontage.
3. Section 506.3, Allowable building area increase due to automatic sprinkler system installation.
4. Section 507, Unlimited area buildings.
b. For open parking structures, see Section 406.3.
c. For private garages, see Section 406.1.
d. See Section 415.5 for limitations.

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.