Section 421 - HYDROGEN CUTOFF ROOMS
Subsection 421.6 - Gas detection system
Current through Register 1531, September 27, 2024
Hydrogen cutoff rooms shall be provided with an approved flammable gas detection system in accordance with Sections 421.6.1 through 421.6.3. [F]
421.6.1 System design. The flammable gas detection system shall be listed for use with hydrogen and any other flammable gases used in the room. The gas detection system shall be designed to activate when the level of flammable gas exceeds 25 percent of the lower flammability limit (LFL) for the gas or mixtures present at their anticipated temperature and pressure. [F]
421.6.2 Operation. Activation of the gas detection system shall result in all of the following: [F]
421.6.3 Failure of the gas detection system. Failure of the gas detection system shall result in activation of the mechanical ventilation system, cessation of hydrogen generation and the sounding of a trouble signal in an approved location. [F]