Section 405 - UNDERGROUND BUILDINGS
Subsection 405.8 - Standby power
Universal Citation: 780 CMR MA Code of Regs 405.8
Current through Register 1531, September 27, 2024
A standby power system complying with Chapter 27 shall be provided standby power loads specified in Section 405.8.1. [F]
405.8.1 Standby power loads. The following loads are classified as standby power loads: [F]
1. Smoke control system.
2. Ventilation and automatic fire detection
equipment for smokeproof enclosures.
3. Fire pumps.
Standby power shall be provided for elevators in accordance with Section 3003.
405.8.2 Pick-up time. The standby power system shall pick up its connected loads within 60 seconds of failure of the normal power supply. [F]
Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.