New low-rise (three stories or less) residential buildings including townhouses shall require a HERS (Home Energy Rating System) index rating as verified by a RESNET (Residential Energy Services Network) certified HERS rater.
1. For units equal to or greater than 3,000 sq. ft. in conditioned floor space, a HERS rating of 65 or less is required.
2. For units less than 3,000 sq. ft., a HERS rating of 70 or less is required.
3. In addition, all new construction shall demonstrate compliance with the Energy Star Qualified Homes Thermal Bypass Inspection Checklist1
Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.