Section 3007 - FIRE SERVICE ACCESS ELEVATOR
Subsection 3007.7 - Electrical power
Universal Citation: 780 CMR MA Code of Regs 3007.7
Current through Register 1531, September 27, 2024
. The following features serving each fire service access elevator shall be supplied by both normal power and Type 60/Class 2/Level 1 standby power:
1. Elevator equipment.
2. Elevator hoistway lighting.
3. Elevator machine room ventilation and cooling equipment.
4. Elevator controller cooling equipment.
3007.7.1
Protection of wiring or
cables. Wires or cables that provide normal and standby power, control
signals, communication with the car, lighting, heating, air conditioning,
ventilation and fire-detecting systems to fire service access elevators shall
be protected by construction having a minimum 1-hour fire-resistance
rating or shall be circuit integrity cable having a minimum 1-hour
fire-resistance rating.
Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.