Section 2702 - EMERGENCY AND STANDBY POWER SYSTEMS [F]
Subsection 2702.1 - Installation
Universal Citation: 780 CMR MA Code of Regs 2702.1
Current through Register 1531, September 27, 2024
Emergency and standby power systems required by this code or the International Fire Code shall be installed in accordance with this code, NFPA 110 and 111. [F]
2702.1.1 Stationary generators. Stationary emergency and standby power generators required by this code shall be listed in accordance with UL 2200. [F]
Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.