Section 2403 - GENERAL REQUIREMENTS FOR GLASS
Subsection 2403.4 - Interior glazed areas

Universal Citation: 780 CMR MA Code of Regs 2403.4
Current through Register 1531, September 27, 2024

Where interior glazing is installed adjacent to a walking surface, the differential deflection of two adjacent unsupported edges shall not be greater than the thickness of the panels when a force of 50 pounds per linear foot (plf) (730 N/m) is applied horizontally to one panel at any point up to 42 inches (1067 mm) above the walking surface.

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.