Structures of conventional light-frame construction in Seismic Design Category D or E, as determined in Section 1613, shall conform to Sections 2308.12.1 through 2308.12.9, in addition to the requirements for Seismic Design Category B or C in Section 2308.11.
2308.12.1 Number of stories. Structures of conventional light-frame construction shall not exceed one story above grade plane in Seismic Design Category D or E.
2308.12.2 Concrete or masonry. Concrete or masonry walls and stone or masonry veneer shall not extend above a basement.
Exception: Stone and masonry veneer is permitted to be used in the first story above grade plane in Seismic Design Category D, provided the following criteria are met:
2308.12.3 Braced wall line spacing. Spacing between interior and exterior braced wall lines shall not exceed 25 feet (7620 mm).
2308.12.4 Braced wall line sheathing. Braced wall lines shall be braced by one of the types of sheathing prescribed by Table 2308.12.4 as shown in Figure 2308.9.3. The sum of lengths of braced wall panels at each braced wall line shall conform to Table 2308.12.4. Braced wall panels shall be distributed along the length of the braced wall line and start at not more than 8 feet (2438 mm) from each end of the braced wall line. Panel sheathing joints shall occur over studs or blocking. Sheathing shall be fastened to studs, top and bottom plates and at panel edges occurring over blocking. Wall framing to which sheathing used for bracing is applied shall be nominal 2-inch wide [actual 11/2 inch (38 mm)] or larger members.
Cripple walls having a stud height exceeding 14 inches (356 mm) shall be considered a story for the purpose of this section and shall be braced as required for braced wall lines in accordance with Table 2308.12.4. Where interior braced wall lines occur without a continuous foundation below, the length of parallel exterior cripple wall bracing shall be one and one-half times the lengths required by Table 2308.12.4. Where the cripple wall sheathing type used is Type S-W and this additional length of bracing cannot be provided, the capacity of Type S-W sheathing shall be increased by reducing the spacing of fasteners along the perimeter of each piece of sheathing to 4 inches (102 mm) o.c.
TABLE 2308.12.4 WALL BRACING IN SEISMIC DESIGN CATEGORIES D AND E (Minimum Length of Wall Bracing per each 25 Linear Feet of Braced Wall Linea)
CONDITION | SHEATHING TYPEb | SDS < 0.50 | 0.50 <= SDS< 0.75 | 0.75 <= SDS <= 1.00 | SDS>1.00 |
One story | G-Pc | 10 feet 8 inches | 14 feet 8 inches | 18 feet 8 inches | 25 feet 0 inches |
S-W | 5 feet 4 inches | 8 feet 0 inches | 9 feet 4 inches | 12 feet 0 inches |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. Minimum length of panel bracing of one face of the wall for S-W sheathing or both faces of the wall for G-P sheathing; h/w ratio shall not exceed 2:1. For S-W panel bracing of the same material on two faces of the wall, the minimum length is permitted to be one-half the tabulated value but the h/w ratio shall not exceed 2:1 and design for uplift is required. b. G-P = gypsum board, fiberboard, particleboard, lath and plaster or gypsum sheathing boards; S-W = wood structural panels and diagonal wood sheathing. c. Nailing as specified below shall occur at all panel edges at studs, at top and bottom plates and, where occurring, at blocking: For 1/2-inch gypsum board, 5d (0.113 inch diameter) cooler nails at 7 inches on center; For 5/8-inch gypsum board, No. 11 gage (0.120 inch diameter) at 7 inches on center; For gypsum sheathing board, 13/4 inches long by 7/16-inch head, diamond point galvanized nails at 4 inches on center; For gypsum lath, No. 13 gage (0.092 inch) by 11/8 inches long, 19/64-inch head, plasterboard at 5 inches on center; For Portland cement plaster, No. 11 gage (0.120 inch) by 11/2 inches long, 7/16- inch head at 6 inches on center; For fiberboard and particleboard, No. 11 gage (0.120 inch) by 11/2 inches long, 7/16-inch head, galvanized nails at 3 inches on center. |
2308.12.5 Attachment of sheathing. Fastening of braced wall panel sheathing shall not be less than that prescribed in Table 2308.12.4 or 2304.9.1. Wall sheathing shall not be attached to framing members by adhesives.
2308.12.6 Irregular structures. Conventional light-frame construction shall not be used in irregular portions of structures in Seismic Design Category D or E. Such irregular portions of structures shall be designed to resist the forces specified in Chapter 16 to the extent such irregular features affect the performance of the conventional framing system. A portion of a structure shall be considered to be irregular where one or more of the conditions described in Items 1 through 6 below are present.
Exception: Floors with cantilevers or setbacks not exceeding four times the nominal depth of the floor joists [see Figure 2308.12.6(2)] are permitted to support braced wall panels provided:
Exception: Portions of roofs or floors that do not support braced wall panels above are permitted to extend up to 6 feet (1829 mm) beyond a braced wall line [see Figure 2308.12.6(4)].
Exception: Braced wall panels are permitted to extend over an opening not more than 8 feet (2438 mm) in width where the header is a 4-inch by 12-inch (102 mm by 305 mm) or larger member.
Exception: Framing supported directly by foundations need not be lapped or tied directly together.
FIGURE 2308.12.6(1) BRACED WALL PANELS OUT OF PLANE
For SI: 1 foot = 304.8 mm. |
FIGURE 2308.12.6(2) BRACED WALL PANELS SUPPORTED BY CANTILEVER OR SET BACK
FIGURE 2308.12.6(3) FLOOR OR ROOF NOT SUPPORTED ON ALL EDGES
For SI: 1 foot = 304.8 mm. |
FIGURE 2308.12.6(4) ROOF OR FLOOR EXTENSION BEYOND BRACED WALL LINE
For SI: 1 foot = 304.8 mm. |
FIGURE 2308.12.6(5) BRACED WALL PANEL EXTENSION OVER OPENING
FIGURE 2308.12.6(6) PORTIONS OF FLOOR LEVEL OFFSET VERTICALLY
FIGURE 2308.12.6(7) BRACED WALL LINES NOT PERPENDICULAR
FIGURE 2308.12.6(8) OPENING LIMITATIONS FOR FLOOR AND ROOF DIAPHRAGMS
2308.12.7 Anchorage of exterior means of egress components. Exterior egress balconies, exterior exit stairways and similar means of egress components shall be positively anchored to the primary structure at not over 8 feet (2438 mm) o.c. or shall be designed for lateral forces. Such attachment shall not be accomplished by use of toenails or nails subject to withdrawal.
2308.12.8 Sill plate anchorage. Sill plates shall be anchored with anchor bolts with steel plate washers between the foundation sill plate and the nut, or approved anchor straps load rated in accordance with Section 1716.1. Such washers shall be a minimum of 0.229 inch by 3 inches by 3 inches (5.82 mm by 76 mm by 76 mm) in size. The hole in the plate washer is permitted to be diagonally slotted with a width of up to 3/16 inch (4.76 mm) larger than the bolt diameter and a slot length not to exceed 13/4 inches (44 mm), provided a standard cut washer is placed between the plate washer and the nut.
2308.12.9 Sill plate anchorage in Seismic Design Category E. Steel bolts with a minimum nominal diameter of 5/8 inch (15.9 mm) or approved foundation anchor straps load rated in accordance with Section 1716.1 and spaced to provide equivalent anchorage shall be used in Seismic Design Category E.